Bit = 0: The function "Bumpless switchover to automatic mode for valves, motors and dosers"
works when switching via the faceplate and switching using interconnectable inputs
AutModLi
and
ManModLi
(
ModLiOp = 1
).
Bit = 1: The "Bumpless switchover in automatic mode for valves, motors and dosers" function
only works for switching via the faceplate. Bumping switchover can be activated via the inputs
AutModLi
and
ManModLi
(
ModLiOp = 1
).
4.10
Control priority in the event of an invalid input command
Feature2 Bit
Number of the
Feature
2 bit: 3
Control priority in the event of an invalid input command
You can use this function to define the control priority in the event of an invalid input command.
Default setting: 0
Bit = 0: In the event of an invalid input command, the control output is retained.
Bit = 1: In the event of an invalid input command, the control output switches to the "neutral
position".
4.11
Reaction to the out of service mode
Feature bit
Number of the
Feature
bit: 1
Reaction to the Out of service mode
You can use this
Feature
bit to define the response of the technological block depending on
the connectable input parameter
OosLi = 1
or
Oos2Li = 1
.
The default setting is 0.
● Bit = 0: The symbol for the "In progress" status (see below) appears in the block icon and in
the faceplate of the assigned technologic block. A change 0-1 in the edge of the input
parameter
OosLi
or
Oos2Li
has no further influence on the response of the technological
block, the initial status is retained. No switch to the "Out of service" mode is performed.
● Bit = 1: The mode switches to "Out of service" assuming that the block is "On" or "Manual"
mode. If this is not the case, the mode does not change. The symbol for the "In progress"
(see below) status also appears in the block icon and in the faceplate of the assigned
technologic block regardless of the mode change. No message is output to indicate whether
or not the mode change took place.
The status display for "In progress" appears as follows:
Configurable response using the Feature I/O
4.11 Reaction to the out of service mode
SITRANS Library for PCS 7
54
Function Manual, 05/2019, A5E35351976-11
Содержание SITRANS PCS 7
Страница 12: ...Table of contents SITRANS Library for PCS 7 12 Function Manual 05 2019 A5E35351976 11 ...
Страница 38: ...Functions of the faceplates 2 4 Trend view SITRANS Library for PCS 7 38 Function Manual 05 2019 A5E35351976 11 ...
Страница 190: ...SITRANS LUT400 6 2 PLut400 SITRANS Library for PCS 7 190 Function Manual 05 2019 A5E35351976 11 ...
Страница 320: ...SIPART PS2 PA 8 1 SipPS2PA SITRANS Library for PCS 7 320 Function Manual 05 2019 A5E35351976 11 ...
Страница 418: ...SITRANS P 10 2 SitraPDr SITRANS Library for PCS 7 418 Function Manual 05 2019 A5E35351976 11 ...
Страница 458: ...SITRANS P PA 11 1 SitrP_PA SITRANS Library for PCS 7 458 Function Manual 05 2019 A5E35351976 11 ...
Страница 542: ...SITRANS FC430 12 2 SiFC43Dr SITRANS Library for PCS 7 542 Function Manual 05 2019 A5E35351976 11 ...
Страница 640: ...SITRANS FC430 PA 13 4 FbFC43PA SITRANS Library for PCS 7 640 Function Manual 05 2019 A5E35351976 11 ...
Страница 676: ...SITRANS LR PA 14 1 SitrLRPA SITRANS Library for PCS 7 676 Function Manual 05 2019 A5E35351976 11 ...
Страница 712: ...SITRANS LR HART 15 1 SitrLRHA SITRANS Library for PCS 7 712 Function Manual 05 2019 A5E35351976 11 ...
Страница 776: ...MultiRanger 200 16 3 Mr200Dia SITRANS Library for PCS 7 776 Function Manual 05 2019 A5E35351976 11 ...
Страница 812: ...SITRANS LU HART 17 1 SitrLuHA SITRANS Library for PCS 7 812 Function Manual 05 2019 A5E35351976 11 ...
Страница 838: ...Driver blocks 18 5 PiSA256H SITRANS Library for PCS 7 838 Function Manual 05 2019 A5E35351976 11 ...
Страница 850: ...Index SITRANS Library for PCS 7 850 Function Manual 05 2019 A5E35351976 11 ...