Diagnostics and troubleshooting
9.4 Status messages according to NE 107
Code
Text message
Cause
Rectification
no measured value
available
Clean the antenna system
F017
Adjustment span too
small
Adjustment not within specification
Change adjustment according to the
limit values (difference between min.
and max. ≥ 10 mm)
F025
Error in the
linearization table
Index markers are not continuously
rising, for example illogical value pairs
Check linearization table
Delete table/Create new
F036
No operable software
Checksum error if software update
failed or aborted
Repeat software update
Send transmitter for repair
F040
Error in the
electronics
Limit value exceeded in signal
processing
Hardware error
Restart transmitter
Send transmitter for repair
F080
General software
error
General software error
Restart transmitter
F105
Determine measured
value
The transmitter is still in the start
phase, the measured value could not
yet be determined
Wait for the end of the switch-on
phase
Duration up to 3 minutes depending
on the measurement environment
and parameter settings
F260
Error in the calibration
Checksum error in the calibration
values
Error in the EEPROM
Send transmitter for repair
F261
Error in the
transmitter settings
Error during setup
Auto false echo suppression faulty
Error when carrying out a reset
Repeat setup
Carry out a reset
F265
Measurement
function disturbed
Program sequence of the measuring
function disturbed
Device restarts automatically
Function check
Code
Text message
Cause
Rectification
C700
Simulation active
A simulation is active
Finish simulation
Wait for the automatic end after
60 mins.
32
SITRANS LR140
Operating Instructions, 08/2020,
A5E50352144
Содержание SITRANS LR140
Страница 6: ...Preface Editing status 2020 08 03 SITRANS LR140 Operating Instructions 08 2020 A5E50352144 v ...
Страница 7: ...Preface vi SITRANS LR140 Operating Instructions 08 2020 A5E50352144 ...
Страница 13: ...Safety notes 2 7 Security information 6 SITRANS LR140 Operating Instructions 08 2020 A5E50352144 ...
Страница 31: ...Setup with smart device Bluetooth 7 1 Connecting 24 SITRANS LR140 Operating Instructions 08 2020 A5E50352144 ...
Страница 49: ...Service and maintenance 10 2 Disposal 42 SITRANS LR140 Operating Instructions 08 2020 A5E50352144 ...
Страница 51: ...Certificates and approvals 11 2 EU conformity 44 SITRANS LR140 Operating Instructions 08 2020 A5E50352144 ...
Страница 57: ...Technical data and dimensions 12 4 Trademark 50 SITRANS LR140 Operating Instructions 08 2020 A5E50352144 ...