Menu diagrams
A.3 Current output
MAG 6000 I / MAG 6000 I Ex de transmitter
76
Operating Instructions, 04/2016, A5E02083319-AG
1)
When batch is selected on digital output or relay, Totalizer 2 is not shown because it is controlled
by the batch function.
2)
The unit "BBL42" in the volume unit list is placed on the space for the customer unit (former "?").
The unit is shown as "BBL42" with the fitting conversion factor of 0.158987 m3, if not overwritten
with customer's own unit text setup using PDM or ordered by using the Z-option Y20 in the
ordering system.
The customer unit in the time unit list is displayed as "?". Via PDM or Y20 option this could e.g.
be chosen as year "y".
A.3
Current output
1)
If HART communication is installed, it is not possible to set the output for 0-20 mA (even
though the option is visible in the display). This is due to the fact that HART does not work if
the output falls below 2-3 mA.
2)
4-20 mA + Alarm is the default setting for MAG 6000 I. For all other variants, the default setting
is 4-20 mA.
3)
For MAG 6000 I only: The controlling of alarm levels does not recognize if the jumper is
mounted for passive output. Do not combine differentiation and low alarm level together with
passive output. The output will try to pull down the level to 1.3 mA at fatal errors which is not
possible for passive output.