Installing / Mounting
4.3 Sensor orientation
SITRANS F C MC2
18
Operating Instructions, 10/2009, A5E02154544-02
Installation in a drop line
Table 4- 2
Installation in dropline
Min. pressure: 0.2 Bar
Installation in a dropline is only possible if a pipeline reduction (A) or orifice (B) with a smaller
cross-section can be installed to prevent the sensor from being partially drained during the
measurements.