Modbus RTU RS-485
35
SFIDK.PS.023.D2.02
APPENDIX H
APPENDIX H
Float Definition
Stuffing of multi-byte numbers into multiple Modbus RTU registers differs among Modbus
devises.
„
Big Endian
“ and „
Little Endian
“ describe the order or sequence in which multi-byte data is stored
in memory. This device uses (as IEEE and Honeywell) a ‘
Big-Endian
’ representation for
addresses and data items. This means that when a numerical quantity larger than a single byte
is transmitted, the
MOST
significant byte is sent first.
Read absolute massflow (4:03001)
Query:
01,03,0B,B8,00,02,46,0A
Response:
01,03,04,
40,C3,52,93
,62,C8
Absolute massflow = 6.10383 kg/s
Value
IEEE FP B
Register N
Register N + 1
(decimal)
MSB LSB
high
low
high
low
100.0
42C80000h
42h
C8h
00h
00h
55.32
425D47AEh
42h
5Dh
47h
AEh
2.0
40000000h
40h
00h
00h
00h
1.0
3F800000h
3Fh
80h
00h
00h
-1.0
BF800000h
bFh
80h
00h
00h