Modbus RTU RS-485
33
SFIDK.PS.023.D2.02
APPENDIX E & F
The Modbus module uses the following Modbus exception codes, when responding to a
master
module:
Exception code (Dec)
Exception name
01
Illegal function
02
Illegal data address
03
Illegal data value
04
Slave device failure
06
Device busy
APPENDIX E
Exception codes
If an exception code 04 is received, further requests have to be done to narrow down the exact
problem.
If any doubts about the address that failed, „
Last Coil/HoldReg ErrorAddr
“ can be read. This will
return the faulty address.
Modbus
Modbus
No. of
Data
Read/
register
address
bytes
type
Description
write
4:00681
680
2
Word
Last Coil ErrorAddr
(Modbus cmd: 1 or 5)
R
4:00682
681
2
Word
Last Coil ErrorNo
(127 = No error)
R
4:00683
682
2
Word
Last HoldReg ErrorAddr
(Modbus cmd: 3 or 16)
R
4:00684
683
2
Word
Last HoldReg ErrorNo
(127 = No error)
R
Reading „
Last Coil/HoldReg ErrorNo
“ will return a detailed error reason. A list of error numbers
can be seen below.
Error
Error
Number
Number
Error name
Reason
(Dec)
(Hex)
3
3
Write access denied
This parameter is in a state where it is
not writable
4
4
Max. limit
The value was greater than the allowed
maximum value
5
5
Min. limit
The value was less than the allowed
minimum value
127
7F
No error
No problem
APPENDIX F
Run Indicator
The
Run Indicator
indicates the state of the device. Two states are possible: ON (0xFF) and OFF
(0x00). The device will be in state ON, unless a serious error is present.
The following errors can turn the state to OFF:
•
When a
„Fatal Error“
is active on the
„Error Pending List“
•
Boot up problems when powering up the flowmeter.
•
If no measurement are delivered or the time between them is too high.
The last condition will be based on the following:
Only the internally broadcasted flow-value is checked. The expected broadcast-rate is read at
power up. If a broadcast is not received after 10 times the expected broadcast rate, the broadcast
rate is re-read from the USM (it may have been changed since power up). If the broadcast rate
was not changed (and the rate was not zero), the
Run Indicator
is set OFF. Reception of ten
broadcasted (flow-) values within 10 times the expected window will set the run-indicator TRUE
again.