![Siemens SITRANS AW 7MP3112 Series Скачать руководство пользователя страница 69](http://html.mh-extra.com/html/siemens/sitrans-aw-7mp3112-series/sitrans-aw-7mp3112-series_operating-instructions-manual_1265484069.webp)
Adapter in 4 ... 20 mA supply mode
The operating range is limited with high measuring currents reaching 22 mA.
Temperature limitation in case of electric current
Max. no-load voltage of the field device
4 mA
22 mA
8 V
-40 °C
-30 °C
10 V
-40 °C
-30 °C
12 V
-40 °C
-30 °C
14 V
-40 °C
-25 °C
16 V
-40 °C
-25 °C
18 V
-40 °C
-
20 V
-40 °C
-
22 V
-40 °C
-
Adapter in multidrop mode
Temperature limitation in case of start-up current
1)
No-load voltage
of the field device
4 mA
6 mA
8 mA
10 mA
12 mA
14 mA
16 mA
18 mA
20 mA
22 mA
8 V
-40 °C
-40 °C
-40 °C
-40 °C
-40 °C
-40 °C
-40 °C
-40 °C
-40 °C
-40 °C
10 V
-40 °C
-40 °C
-40 °C
-40 °C
-40 °C
-40 °C
-40 °C
-40 °C
-35 °C
-35 °C
12 V
-40 °C
-40 °C
-40 °C
-40 °C
-40 °C
-40 °C
-40 °C
-40 °C
-35 °C
-35 °C
14 V
-40 °C
-40 °C
-40 °C
-40 °C
-40 °C
-40 °C
-35 °C
-35 °C
-35 °C
-35 °C
16 V
-40 °C
-40 °C
-40 °C
-40 °C
-40 °C
-35 °C
-35 °C
-35 °C
-30 °C
-30 °C
18 V
-40 °C
-40 °C
-40 °C
-40 °C
-40 °C
-35 °C
-35 °C
-30 °C
-30 °C
-25 °C
20 V
-40 °C
-40 °C
-40 °C
-35 °C
-35 °C
-35 °C
-30 °C
-30 °C
-25 °C
-25 °C
22 V
-40 °C
-40 °C
-40 °C
-35 °C
-35 °C
-35 °C
-30 °C
-30 °C
-25 °C
-25 °C
1)
Information of start-up current is available in the following sections:
● Configuring power supply (Page 58)
● Optimization of the power supply (supply by the adapter) (Page 61)
A.2
Spare parts and accessories
Various accessories and spare parts are available for the WirelessHART adapter and can be
ordered separately:
● Battery unit SITRANS AW200
● Mounting support, wall/pipe
● Adapter set M20,
● Adapter set NPT 1/2
Appendix
A.2 Spare parts and accessories
WirelessHART Adapter SITRANS AW200
Operating Instructions, 02/2020, A5E02777161-AA
69