4
3ZX1012-0SE50-0AA0
Connection designation according to EN 50013
The switching point of snap-action contacts remains constant throughout the
whole service life independent of contact erosion.
Current carrying capacity AC15 / DC13
Exchanging the actuator head
The part-turn actuator is pre-stressed and must be held in position!
Unscrew enclosure cover (
1
), turn locking plate (
2
) to the right, pull off actuator
head (
3
).
Insert new actuator head (
3
) as far as it goes, turn locking plate (
2
) to the left,
screw on enclosure cover (
1
).
Part-turn actuator 3SE5000-0AH00
(left or right-hand switching)
Setting the actuator head for either left or right-hand switching (at the fac-
tory)
Actuator plunger (
4
) turned to the left by 90° = left-hand switching.
Actuator plunger (
4
) turned to the right by 90° = right-hand switching.
Actuation speed V
min
Snap-action contact
0.1 mm/s
Slow-action contact
10 mm/s
Minimum force required in actuation direction:
3SE51..-..
E
,
F, R, V1
9 N
3SE51..-..
C
,
D
18 N
Minimum torque in actuation direction:
3SE51..-..
H
,
T
0.25 Nm
Drive (Figure 1.1.2)
Minimum torque in actuation direction:
0.40 Nm
3SE51..-..... / 3SE52..-.....
Switching angle:
3SE51..-..U1. / 3SE52..-..U1.
5°
3SE51..-..U2. / 3SE52..-..U2.
15°
Contact Blocks
Contact
version
Figure Name
Circuit diagram MLFB
3SE5000
1NO/1NC 2.1.1 Standard, snap-action
–.C...
1NO/1NC 2.1.4 Standard, slow-action
–.B...
–.R...
1NO/2NC 2.1.5 Standard, snap-action
–.L...
1NO/2NC 2.1.6 Standard, slow-action
–.K...
–.Q...
Technical Data
Degree of protection according to DIN VDE 0470 and IEC 60529:
3SE5112-.....-1DA0
IP66 / IP67
3SE5122-.....-1DA0
IP66 / IP67
For actuator heads R, H80 to H83, K80 to K83
IP65 / IP67
Permissible ambient temperature during operation –25 ... +85 °C
Storage temperature
–40 ... +90 °C
Maximum surface temperature
105° C
Degree of pollution according to DIN VDE 0110
Class 3
Mechanical service life
15 x 10
6
operating cycles
Exception for 3SE5...-.
CR
..
10 x 10
6
operating cycles
Exception for 3SE51..-..
T
..
5 x 10
6
operating cycles
Electrical service life
10 x 10
6
operating cycles
(with contactor 3RH11, 3RT1016 to 3RT1026)
Utilization category I
e
/AC-15
100,000 operating cycles
3-pole contact block
240 V 1.5 A
2-pole contact block
240 V 3 A
Switching frequency
6000 operating cycles / hour
(with contactor 3RH11, 3RT1016 to 3RT1026)
Shock resistance (IEC 60068-2-27)
30 g / 11 ms
Repeat accuracy
0.05 mm
(Repeated switching, measured at the plunger of the contact block)
Rated insulation voltage U
i
400 V
Rated impulse voltage U
imp
6 kV
Rated operational voltage U
e
400 V
at U
e
> 300 V same potential only
Thermal rated current I
th
6 A
Short-circuit protection
(without welding)
DIAZED fuse links
Utilization category gG
6 A
Miniature circuit breaker
Characteristic C
1 A
Rated current I
e
at U
e
:
3-pole
AC15
B300
24 V
6 A
120 V
3 A
240 V
1.5 A
2-pole
AC15
A300
24 V
6 A
120 V
6 A
240 V
3 A
2 / 3-pole
DC13
Q300
24 V
3 A
125 V
0.55 A
250 V
0.27 A
Maintenance
1
2
3
4
4
3