Technical data
11.3 3RU21 thermal overload relays
SIRIUS Innovations - SIRIUS 3RU2 thermal overload relays / SIRIUS 3RB3 solid-state overload relays
Manual, 09/2014, A5E03656507420A/RS-AA/002
115
Type
3RU2116
3RU2126
Size
S00
S0
Width
45 mm
45 mm
Connection type
Spring-loaded connection
•
Operating tool
mm
∅
3.0 x 0.5. ∅ 3.5 x 0.5
•
Conductor cross-sections (min./max.)
- Solid
mm
2
2 x (0.5 to 2.5)
- Finely stranded without end
sleeve
mm
2
2 x (0.5 to 2.5)
- Finely stranded with end sleeve
(DIN 46228 Part 1)
mm
2
2 x (0.5 to 1.5)
- AWG cables, solid or stranded AWG
2 x (20 to 14)
Connection type
Ring cable lug connection
Connection screw
M3, Pozidriv size 2
Operating tool
mm
∅
5 ... 6
Specified tightening torque
Nm
0,8 ... 1,2
Ring cable lugs that can be used
mm
d
22)
= min. 3.2, d
32)
= max. 7.5
•
DIN 46234 without insulating sleeve
•
DIN 46225 without insulating sleeve
•
DIN 46237 with insulating sleeve
•
JIS C2805 type R without insulating sleeve
•
JIS C2805 type RAV with insulating sleeve
•
JIS C2805 type RAP with insulating sleeve
1)
If two different conductor cross-sections are being connected to one clamping point, both cross-sections must be
located in the range indicated. If identical cross-sections are used, this restriction does not apply.
2)