Technical data for current and short-circuit protection
Adjustable response current of
the current-dependent overload
release
Design of the fuse
link for short-circuit
protection of the main
circuit necessary
Trip class
Active power loss
total typical
initial value
final value
A
A
W
3RU2136-4A.. 11
16
fuse gL/gG: 40 A
CLASS 10
8
3RU2136-4B.. 14
20
Fuse gL/gG: 50 A
CLASS 10
8
3RU2136-4D.. 18
25
fuse gL/gG: 63 A
CLASS 10
8
3RU2136-4E.. 22
32
Fuse gL/gG: 80 A
CLASS 10
11
3RU2136-4F.. 28
40
Fuse gL/gG: 80 A
CLASS 10
11
3RU2136-4G.. 36
45
fuse gL/gG: 100 A
CLASS 10
11
3RU2136-4H.. 40
50
fuse gL/gG: 100 A
CLASS 10
11
3RU2136-4Q.. 47
57
fuse gL/gG: 100 A
CLASS 10
11
3RU2136-4J..
54
65
fuse gL/gG: 125 A
CLASS 10
12
3RU2136-4K.. 62
73
fuse gL/gG: 160 A
CLASS 10A
13
3RU2136-4R.. 70
80
fuse gL/gG: 160 A
CLASS 10A
14
Technical data for rated operating current UL/CSA
Full-load current (FLA) for 3-phase motor
at 480 V rated value
at 600 V rated value
A
A
3RU2136-4A..
16
16
3RU2136-4B..
20
20
3RU2136-4D..
25
25
3RU2136-4E..
32
32
3RU2136-4F..
40
40
3RU2136-4G..
45
45
3RU2136-4H..
50
50
3RU2136-4Q..
57
57
3RU2136-4J..
65
65
3RU2136-4K..
73
73
3RU2136-4R..
80
80