Technical data
SYS-101A
Operating Instructions, 05/2011, A5E03431563F-01
29
General specifications
Constant coldness in operation
in accordance with EN 60068-2-1, test Ab
-5 °C for 16 h
Constant dry heat in operation
in accordance with EN 60068-2-2
50 °C for 16 h
Cyclic damp heat in operation
in accordance with EN 60068-2-30, Db
+25 °C ... +50 °C
6 cycles
3 h per temperature level
95% rel. humidity
Device-specific data
Installation
Installation in external enclosure possible.
Tested: Siemens ALPHA Box complete cubicle (8GM1040-
3KK30)
Dimensions (W x H x D) in mm
370 x 230 x 150
Weight in g (without packaging)
3000
Permitted ambient temperature ranges/ambient conditions
In operation (in cabinet)
-20 °C ... +45 °C
During storage/transport
-40 °C ... +75 °C
Relative humidity during operation
< 95 %
Installation altitude
Up to 1000 m
Internal heating
No
Electrical data
Supply voltage
400 V ± 10%
Min. input voltage
360 V
Max. input voltage
440 V
Rated insulation voltage
440 V
Rated frequency
50 Hz
Rated input current
18 A
Rated short-circuit current
10 kA
Charging current
16 A
Line system configuration
TNS
Overvoltage protection at input
Internal
Overvoltage protection (e.g. against lightning strike)
Not installed
Number of charging outlets
1
Number of phases for charging outlet
3
Содержание SIPLUS ECC8000
Страница 4: ...Table of contents SYS 101A 4 Operating Instructions 05 2011 A5E03431563F 01 ...
Страница 6: ...Introduction 1 2 Recycling and disposal SYS 101A 6 Operating Instructions 05 2011 A5E03431563F 01 ...
Страница 8: ...Safety instructions SYS 101A 8 Operating Instructions 05 2011 A5E03431563F 01 ...
Страница 14: ...Description 3 5 Application example SYS 101A 14 Operating Instructions 05 2011 A5E03431563F 01 ...
Страница 18: ...Installation SYS 101A 18 Operating Instructions 05 2011 A5E03431563F 01 ...
Страница 22: ...Connection 6 3 Wiring and commissioning SYS 101A 22 Operating Instructions 05 2011 A5E03431563F 01 ...
Страница 24: ...Maintenance and repair SYS 101A 24 Operating Instructions 05 2011 A5E03431563F 01 ...
Страница 26: ...Dimensional drawings SYS 101A 26 Operating Instructions 05 2011 A5E03431563F 01 ...
Страница 36: ...Index SYS 101A 36 Operating Instructions 05 2011 A5E03431563F 01 Transportation 15 V Validity Documentation 5 ...