Requirements of DC power supplies
WARNING
Electric shock when connected to an unsafe power supply
When equipment is connected to an unsafe power supply, exposed components may be at a
hazardous voltage level, which might result in serious injury or death.
The DC power supply must be designed as a circuit of category PELV/DVC A according to IEC/
UL/EN 61800‑5‑1.
WARNING
Electric shock due to inadequately protected power supply cables
If power supply cables are inadequately protected, then lightning strikes can result in a surge
voltage. This can result in death, serious injury and material damage.
In the case of supply lines > 10 m, protectors must be installed at the device input in order to
protect against lightning (surge).
The DC power supply must be connected to the ground/shield of the MCU for EMC and/or
functional reasons. For EMC reasons, this connection should only be made at one point. This
connection is normally provided as standard in the S7-1500 I/Os. In exceptional
circumstances when this is not the case, the ground connection should be made on the
grounding rail of the control cabinet; please also refer to /EMC/EMC Installation Guide.
Table 8-4
DC power supply requirements according to EN 61131-2
Rated voltage
24 VDC
Voltage range (average value)
20.4 VDC to 28.8 VDC
Voltage ripple peak-to-peak
5% (unfiltered 6-pulse rectification)
Ramp-up time at POWER ON
Any
Non-periodic overvoltages
≤ 35 V
Duration of overvoltage
≤ 500 ms
Recovery time
≥ 50 s
Events per hour
≤ 10
Transient voltage interruptions
Outage time
≤ 3 ms
Recovery time
≥ 10 s
Events per hour
≤ 10
Further information
More information about recommended power supply units and tables for calculating the current
drawn for SINAMICS S120 module lineups can be found in the
● SINAMICS S120 Booksize Power Units Manual
Connecting
8.8 Power supply X80
MCU 1720
70
Equipment Manual, 09/2019, A5E47437728B AB
Содержание SINUMERIK MCU1720
Страница 6: ...Table of contents MCU 1720 6 Equipment Manual 09 2019 A5E47437728B AB ...
Страница 10: ...Preface MCU 1720 10 Equipment Manual 09 2019 A5E47437728B AB ...
Страница 44: ...Dimension drawings 6 3 Portrait mounting MCU 1720 44 Equipment Manual 09 2019 A5E47437728B AB ...
Страница 56: ...Installation 7 5 Mounting strain reliefs MCU 1720 56 Equipment Manual 09 2019 A5E47437728B AB ...
Страница 86: ...Service and maintenance 9 1 Troubleshooting MCU 1720 86 Equipment Manual 09 2019 A5E47437728B AB ...
Страница 90: ...Technical specifications 10 3 Recycling and disposal MCU 1720 90 Equipment Manual 09 2019 A5E47437728B AB ...
Страница 96: ...Safety symbols MCU 1720 96 Equipment Manual 09 2019 A5E47437728B AB ...