Configuration
SINAUT MD740-1
61 von 105
File 3172AD001_V1_1_060206.doc
File saved
06.02.2006
File printed
06.02.2006
State Freigabe
Autor Pauluhn
automatic switching to summer or winter time, enter:
CET-1CEST,M3.5.0,M10.5.0/3
Time stamp in file system (2h granularity): Yes / No
If this switch is set to
Yes
, the SINAUT MD740-1 writes the
current system into its memory every 2 hours.
Consequence: If the SINAUT MD740-1 is switched off and then
back on, after being switched on a time in this 2-hour time
window will be displayed and not a time on 1 January 2000.
Services
#
#
#
#
Remote Logging
All log entries take place by default in the flash memory of the
SINAUT MD740-1. If the maximum memory space for these logs is
exhausted, the oldest log entries are automatically overwritten by
new ones.
It is possible to transfer the log entries to an external computer.
This is advisable if, for example, logging is to administered
centrally.
Activate remote UDP logging: Yes / No
If all log entries are to be transferred to the external log server
(specified below), set this switch to
Yes
.
Log Server IP address
Enter the IP address of the log server to which the log entries
are to be transferred via UDP.
!
The log server must have a fixed and known IP address.
!
You must enter the IP address, not a hostname. Name
resolution is not supported here because otherwise the
breakdown of a DNS server could not be reported.
Log Server port
Enter the port of the log server to which the log entries are to be
transferred via UDP. Default: 514