Technical Data
SINAUT MD740-1
103 von 105
File 3172AD001_V1_1_060206.doc
File saved
06.02.2006
File printed
06.02.2006
State Freigabe
Autor Pauluhn
8 Technical
Data
Application Interface
10/100 Base-T (RJ45 plug)
Ethernet IEEE802
10/100 Mbit/s
Service Interface
DSUB-9 plug, PIN assignment RS232
Virtual Private Network
Protocol: IPSec (tunnel and transport mode)
Encryption: 3DES, AES, DES
Packet authentication: MD5, SHA-1
Internet Key Exchange (IKE), authentication: Pre-Shared
Key (PSK), X.509v3 certificates
NAT-T, DynDNS, Dead Peer Detection (DPD)
Firewall
Stateful Packet Inspection
Anti-Spoofing
NAT (IP Masquerading)
Port Forwarding
Other
DNS Cache, DHCP Server, NTP, Remote Logging
Management
Web based administration
Connection
GPRS: Multislot class 10;
Coding schemes: CS-1, CS-2, CS-3, CS-4
Transmission Power
Quad Band; GSM 850 MHz: max. 2 Watt, GSM 900
MHz: max. 2 Watt, DCS 1800 MHz: max. 1 Watt, PCS
1900 MHz: max. 1 Watt
Antenna Connection
Impedance nominal: 50 Ohm, socket: SMA
Power supply
Un 18-30 VDC
In 450-260mA ; Iburst = 1,3 A
Temperature range
Operating:
-20 °C up to +50 °C
Storage:
-40 °C up to +85 °C
Humidity:
0-95 %, not condensing
Mechanics
Construction:
top-hat rail housing
Material:
synthetic material
Protection class: IP20
Dimensions:
114 mm x 45 mm x 99 mm
Weight:
approx. 280g
Approvals
CE
R&TTE (GSM)
GSM/GPRS engine with GCF approval
EMV/ESD: EN
55024
EN 55022 Class A
EN
61000-6-2
Electrical safety:
EN 60950