A.1.4.2
Configuring Modbus TCP via interface X150
Activate Modbus TCP via X150 (CU320-2 PN or CU310-2 PN)
1. For drive object DO1, set p2030 = 13 (Modbus TCP).
2. Using p8921, set the IP address for the onboard PROFINET interface on the Control Unit.
3. Set the standard gateway using p8922.
4. Set the subnet mask using p8923.
5. Set the DHCP mode using p8924.
6. Select "Activate and save configuration" as interface configuration using p8925 = 2.
7. In the STARTER commissioning tool, check the list of drive object p0978.
When required, change the sequence of the drive objects using the telegram configuration
("Drive device" > "Communication" > "Telegram configuration").
8. Save the settings in the STARTER commissioning tool and carry out a POWER ON.
Modbus settings with interface X150
Using the following parameters, set the communication for Modbus TCP with a X150 interface:
Parameters
Explanation
p2040
Setting the monitoring time to monitor the received process data via fieldbus inter‐
face.
If process data is not transferred within one cycle of the fieldbus monitoring time,
then the drive shuts down with fault F01910.
r2050[0...19]
Connector output to interconnect the PZD received from the fieldbus controller via
IF1.
p2051[0...24]
Selects the PZD (actual values) to be sent to the fieldbus controller in the word format
via IF1.
r2053[0...24]
Displays the PZD (actual values) sent to the fieldbus controller in the word format via
IF1.
r2054
Status display for the internal communication interface.
p8839[0...1]
Assigning the PN onboard interface (x150) via PZD interface 1 (IF1) and interface 2
(IF2).
r8850[0...19]
Connector output to interconnect the PZD (setpoints) received in the word format via
IF2.
p8851[0...24]
Selects the PZD (actual values) to be sent in the word format via IF2.
r8853[0...24]
Displays the PZD (actual values) sent in the word format via IF2.
r8854
Status display for COMM BOARD.
Communication
A.1 Communication
Industrial Security
Configuration Manual, 08/2017, A5E36912609A
177
Содержание SINAMICS
Страница 6: ...Table of contents Industrial Security 6 Configuration Manual 08 2017 A5E36912609A ...
Страница 8: ...Introduction Industrial Security 8 Configuration Manual 08 2017 A5E36912609A ...
Страница 18: ...Industrial Security 3 4 Security management Industrial Security 18 Configuration Manual 08 2017 A5E36912609A ...
Страница 222: ...Communication A 1 Communication Industrial Security 222 Configuration Manual 08 2017 A5E36912609A ...
Страница 224: ...Service Support Industrial Security 224 Configuration Manual 08 2017 A5E36912609A ...