Error
value
Significance
Remark
Additional
info
0x7F
Parameter %s [%s]: Write access only
in the commissioning state, device
(device: p0009 not equal to 0).
–
–
0x81
Parameter %s [%s] must not be writ‐
ten during download.
–
–
0x82
Transfer of master control is blocked
by BI: p0806.
–
–
0x83
Parameter %s [%s]: Requested BICO
interconnection not possible.
BICO output does not supply float values. The BICO input,
however, requires a float value.
–
0x84
Parameter %s [%s]: Parameter
change inhibited
(refer to p0300, p0400, p0922)
–
–
0x85
Parameter %s [%s]: Access method
not defined.
–
–
0x87
Write job will not be executed.
The write request is rejected because know-how protection is
active.
–
0xC8
Below currently valid limit.
Modification request for a value that, although within "abso‐
lute" limits, is below the currently valid lower limit.
–
0xC9
Above currently valid limit.
Modification request for a value that, although within "abso‐
lute" limits, is above the currently valid lower limit (e.g. gov‐
erned by the current converter rating).
–
0xCC
Write access not permitted.
Write access is not permitted because an access code is not
available.
–
Determining the drive object numbers
Further information about the drive system (e.g. drive object numbers) can be determined as
follows using parameters p0101, r0102, and p0107/r0107:
1. The value of parameter r0102 ("Number of drive objects") for drive object/axis 1 is read via
a read request.
Drive object 1 is the Control Unit (CU) which is a minimum requirement for each drive
system.
2. Depending on the result of the initial read request, further read requests for drive object 1
are used to read the indices for parameter p0101 "Drive object numbers", as specified by
parameter r0102.
Example:
If the number of drive objects is "5", the values of indices 0 to 4 of parameter p0101 are
read. Of course, the relevant indexes can also be read at once.
3. Following this, parameter r0107/p0107 ("Drive object type") is read for each drive object/
axis (indicated by the drive object number).
Depending on the drive object, parameter 107 can be either an adjustable parameter or a
display parameter.
The value in parameter r0107/p0107 indicates the drive object type. The coding for the
drive object type is specified in the parameter list.
Communication
A.1 Communication
Industrial Security
100
Configuration Manual, 08/2017, A5E36912609A
Содержание SINAMICS
Страница 6: ...Table of contents Industrial Security 6 Configuration Manual 08 2017 A5E36912609A ...
Страница 8: ...Introduction Industrial Security 8 Configuration Manual 08 2017 A5E36912609A ...
Страница 18: ...Industrial Security 3 4 Security management Industrial Security 18 Configuration Manual 08 2017 A5E36912609A ...
Страница 222: ...Communication A 1 Communication Industrial Security 222 Configuration Manual 08 2017 A5E36912609A ...
Страница 224: ...Service Support Industrial Security 224 Configuration Manual 08 2017 A5E36912609A ...