NOTICE
Damage if the auxiliary power supply is not available
When the auxiliary power supply is switched off, data about error message statuses can be
lost. Inadequate diagnostic and error rectification measures can result in material damage.
● We recommend using an uninterruptible power supply (UPS). If you are unsure of the
measures necessary after the device fails, or if a fault cannot be rectified, contact the
Service Center.
After performing repairs, refasten all cable ducts whose cover faces downward with a cable tie.
The cable ties must be located at the same positions as in the delivered state. You will find more
information in "Fastening the cable ducts with cable ties (Page 57)".
NOTICE
Damage caused by an incomplete repair
In the case of damage, several components can have a fault condition. Consequential
damage can occur if the device is recommissioned but the repair work carried out was not
complete.
● Check whether secondary faults have occurred on components which have failed.
Replace the components involved.
Measures in the event of an error
It is not possible to fully test repairs that are carried out on site. Return the defective module
back to the manufacturing plant for repair. The relevant address is available from your Siemens
contact person.
Always enclose the following information:
● Type and serial number
● Time and date of the failure
● Description of the fault profile
Specify what happened when the component failed.
● Operating point, currents and voltages
● Log file with fault messages
● Copy of the CompactFlash card
● If possible, hard copies from the plotter or screenshots
● Mounting location
Specify the equipment identifier. You can find the item code on the component and close to
the slot.
Maintenance
9.6 Repairs
SINAMICS SL150 6SL38655UM427AA02
Operating Instructions Rev.201910281507 EXAMPLE
73
Содержание SINAMICS SL150 6SL38655UM427AA02
Страница 2: ...28 10 2019 15 07 V18 00 ...
Страница 50: ...Mounting 5 2 Torques SINAMICS SL150 6SL38655UM427AA02 50 Operating Instructions Rev 201910281507 EXAMPLE ...
Страница 60: ...Commissioning SINAMICS SL150 6SL38655UM427AA02 60 Operating Instructions Rev 201910281507 EXAMPLE ...
Страница 86: ...Maintenance 9 6 Repairs SINAMICS SL150 6SL38655UM427AA02 86 Operating Instructions Rev 201910281507 EXAMPLE ...
Страница 88: ...Spare parts SINAMICS SL150 6SL38655UM427AA02 88 Operating Instructions Rev 201910281507 EXAMPLE ...
Страница 99: ......
Страница 102: ......
Страница 104: ......