8.4 Up/Download
Intelligent Operating Panel 2 (IOP-2)
56
Operating Instructions, 06/2020, FW V2.6, A5E39549448B AH
The naming of the file follows the normal conventions and is restricted to only the ASCII
character set, but it is suggested that the file name should be in lower case with only
numbers and letters without spaces, followed by the correct file extension.
List of commands
Command
Format
Example
Remarks
Write a parameter
wrp <number> <index>
<value>
wrp 1120 0 5.0
There must be only one
parameter on each line.
Read a parameter
rdpw <param> <index>
<value> <timeout ms>
rdpw 10 0 0 5000
Wait 5 seconds for p10 to go
back to 0
Read a BICO parameter
rdpw <param> <index>
<param> <index> < timeout
ms>
wrp 840 0 722 5 1
Allows 1 ms to confirm the
OFF1 signal is set to Digital
Input 5
Read a BICO parameter 1 or 0 wrp <param> <index> <1/0>
<timeout ms>
wrp 1070 0 1 1
Allows 1 ms to confirm the
signal source is set 100%
Comment
rem <text>
rem This is a comment line
Only one comment on each
line
Downloading procedure
1. Navigate to the Up/Download screen and select "Download: panel to
drive".
2. Select the CLI file to be downloaded to the drive.
3. A progress screen will be displayed, indicating the status of the