3.3.2.9
Door limit switches
Door limit switches monitor the doors. The circuit breaker opens when a door is opened.
The electromechanical door interlocking system prevents access to the power unit while
operational. The following conditions must be fulfilled in order to open the doors: For additional
information, see Chapter "Opening the device (Page 125)".
3.3.2.10
Cooling unit
Operating principle of the re-cooling unit
The re-cooling unit dissipates the heat loss from the drive. The deionized water in the internal
water circuit absorbs the heat of the drive power unit which is to be dissipated, and is pumped
to the heat exchanger by a maintenance-free circulating pump. The warm deionized water is
cooled by the external raw water circuit and pumped back to the drive.
Two pipes are installed in the drive. The cold water of the re-cooling unit flows in one of the
pipes, and is heated by the losses and flows back to the re-cooling unit through the other pipe.
Internal de-ionized water circuit
The internal water circuit is filled with deionized water (deionized, fully-desalinated water). The
conductivity of the cooling water must be ≤ 1 µS/cm in operation.
NOTICE
Inadmissible additives in the deionized water
Inadmissible additives in the deionized water can cause the cooling system to fail. This could
damage the drive.
● Use only deionized water that corresponds to the specifications. The specification of the
deionized water can be found in the documentation for the re-cooling unit.
● The level of the deionized water expansion tank is monitored for any water leakages and the
pump motor circuit breakers are also monitored.
● The pressure of the deionized water is displayed on a manometer.
● The deionized water temperature is measured. The value is used for controlling the three-
way valve
● If one of the monitoring devices responds, a signal is output or the re-cooling unit and drive
are switched off.
Description
3.3 Power unit
SINAMICS GL150 6SL38555UN113KA0Z
36
Operating Instructions Rev.201910281450 EXAMPLE
Содержание SINAMICS GL150
Страница 2: ...28 10 2019 14 50 V18 00 ...
Страница 60: ...Description 3 5 Options SINAMICS GL150 6SL38555UN113KA0Z 60 Operating Instructions Rev 201910281450 EXAMPLE ...
Страница 106: ...Commissioning SINAMICS GL150 6SL38555UN113KA0Z 106 Operating Instructions Rev 201910281450 EXAMPLE ...
Страница 150: ...Spare parts SINAMICS GL150 6SL38555UN113KA0Z 150 Operating Instructions Rev 201910281450 EXAMPLE ...
Страница 162: ...Index SINAMICS GL150 6SL38555UN113KA0Z 162 Operating Instructions Rev 201910281450 EXAMPLE ...
Страница 163: ......
Страница 166: ......
Страница 168: ......