Air-Cooled Chassis Power Units - supplement to Motor Module 6SL3320-1TG41-5AA3
Equipment Manual, 10/2020, A5E50422764A
83
Appendix
A
A.1
Cable lugs
Cable lugs
The cable connections on the devices are designed for cable lugs according to DIN 46234 or
DIN 46235.
For connection of alternative cable lugs, the maximum dimensions are listed in the table
below.
These cable lugs are not to exceed these dimensions, as mechanical fastening and adherence
to the voltage distances is not guaranteed otherwise.
Figure A-1
Dimensions of the cable lugs
Table A- 1
Dimensions of the cable lugs
Screw / bolts
Connection cross-
section
[mm²]
d2
[mm]
b
[mm]
l
[mm]
c1
[mm]
c2
[mm]
M8
70
8.4
24
55
13
10
M10
185
10.5
37
82
15
12
M10
240
13
42
92
16
13
M12
95
13
28
65
16
13
M12
185
13
37
82
16
13
M12
240
13
42
92
16
13
M16
240
17
42
92
19
16