05.2004
Mounting, Connecting-up
Siemens AG
6SE7087-2CX87-2DA0
SIMOVERT MASTERDRIVES
Unità di frenatura / Braking Unit
3-5
3.2 Power
terminals
Construction type S
Construction type A
Construction type B
Connection
Terminal
Tightening
torque
[Nm / lbf ft]
Terminal
Tightening
torque
[Nm / lbf ft]
Terminal
Tightening
torque
[Nm / lbf ft]
C/+ Input
X3:1
0.5 / 0.37
X3:2
2 / 1.5
Busbar C/L+
13 / 9.6
D/-
Input
X3:3
0.5 / 0.37
X3:3
2 / 1.5
Busbar D/L-
13 / 9.6
Shielding
X3:5
0.5 / 0.37
M5 screw on
top of
housing
6 / 4.4
M6 screw on
top of
housing
10 / 7.4
PE1
M5 screw on
top of
housing
6 / 4.4
X3:4
2 / 1.5
Busbar PE1
13 / 9.6
G
external braking
resistor
X6:1
0.5 / 0.37
X6:1
2 / 1.5
Busbar G /
R+
13 / 9.6
H1 internal
braking
resistor
X6:3
0.5 / 0.37
X6:2
2 / 1.5
H2 / H
external braking
resistor
X6:5
0.5 / 0.37
X6:3
2 / 1.5
Busbar H / R-
13 / 9.6
Shielding
X6:7
0.5 / 0.37
M5 screw on
bottom of
housing
6 / 4.4
M6 screw on
top of
housing
10 / 7.4
PE2
M5 screw on
bottom of
housing
6 / 4.4
X6:4
2 / 1.5
Busbar PE2
13 / 9.6
Connection via
Terminal strip
Terminal strip
Cable lug according to DIN
46235 and M8 screws
Connectable
conductor cross-
section
VDE
(mm2)
1.5 to 4
2.5 to 10
max. 1 x 95 or 2 x 70
(stranded):
AWG
16 to 10
14 to 6
max. 1 x 000
NOTE
AWG: American
Wire
Gauge
Recommended conductor cross-sections: see Table 7-1.
Table 3-1
Power terminals of the braking unit
The braking unit may be connected to the DC bus bar with or without
using fuses.
The connections between the drive converter and braking unit must be
short-circuit- and ground-fault proof.
The voltage withstand capability of the cable must be according to the
line voltage.
WARNING