6.6.2
Ground the metal shield in the terminal box
If you are using metal-armored cables that are inserted into the terminal or auxiliary terminal
boxes with non-intrinsically safe circuits, then ground the metal shield in the terminal box.
● In terminal boxes with internal grounding part, connect the metal shield to the internal
grounding point.
● In terminal boxes without internal grounding part, connect the metal shield to one of the
green-yellow grounding terminals.
For explosion-protected motors, it is not permissible to use more than one grounding location
for the metal shield.
6.7
Conductor connection
The maximum conductor cross-section that can be connected is 300 mm².
6.7.1
Inserting the cable into the terminal box
The connection cables are inserted into the terminal box via an exchangeable cable entry plate
or cable entry support. The cable glands are not included in the standard scope of supply.
Table 6-3
Cable entry plate versions
Terminal box
Cable entry plate with boreholes
Option R53 /
Explosion-protected motors
TB3R61
4 x M80 x 2 + 2 x M25 x 1.5
Undrilled
1XB1631
4 x M80 x 2 + 2 x M25 x 1.5
1XB7750
8 x M72 x 2 + 3 x M25 x 1.5
Procedure
1. Unscrew the cable entry plate.
2. When required, drill the required number of holes or threads in the required size into the
cable entry plate. Ensure that the cable entry plate can be assembled after drilling and that
it features sufficient stiffness.
3. Install the cable glands required, taking into account the manufacturers data relating to
installation steps - including tightening torques and the suitability for the ambient conditions.
4. Route the cables through the cable glands - and carefully ensure that the cables and
conductors are strain relieved.
5. Fit the cable entry plate to the terminal box with the assembled cables.
For the TB3R61 and 1XB1631 terminal boxes, ensure a perfectly flat contact surface for the
cover, to ensure that the IP degree of protection is complied with.
Electrical connection
6.7 Conductor connection
1MB5 SH 400/450
76
Operating Instructions, 05/2019, A5E45959221A
Содержание SIMOTICS XP 1MB5 SH400
Страница 2: ......
Страница 10: ...Table of contents 1MB5 SH 400 450 8 Operating Instructions 05 2019 A5E45959221A ...
Страница 64: ...Assembly 5 4 Aligning and fixing the machine 1MB5 SH 400 450 62 Operating Instructions 05 2019 A5E45959221A ...
Страница 106: ...Operation 8 8 Non operational periods 1MB5 SH 400 450 104 Operating Instructions 05 2019 A5E45959221A ...
Страница 154: ...Disposal 11 5 Disposal of components 1MB5 SH 400 450 152 Operating Instructions 05 2019 A5E45959221A ...
Страница 156: ...Service support 1MB5 SH 400 450 154 Operating Instructions 05 2019 A5E45959221A ...
Страница 160: ...Quality documents 1MB5 SH 400 450 158 Operating Instructions 05 2019 A5E45959221A ...
Страница 165: ......
Страница 166: ...Germany More information www siemens com drives Siemens AG Digital Industries Postfach 48 48 90026 NÜRNBERG ...