Electrical connection
6.5 Connecting the temperature sensor/anti-condensation heater
Standard motors SH 63 ... 355
70
Operating Instructions, 12/2018, A5E38483075A
External ground terminal
When making connections, ensure the following:
●
Ensure that the connecting surface is bare and is protected against corrosion using a
suitable substance, e.g. acid-free Vaseline.
●
Position the cable lug between the contact bracket and the grounding bracket; do not
remove the contact bracket pressed into the enclosure!
●
Arrange the flat washer and spring washer under the bolt head.
●
Use the marked connection location for the grounding conductor on the stator housing.
●
Observe the tightening torque for the locking screw.
6.5
Connecting the temperature sensor/anti-condensation heater
6.5.1
Connecting optional integrated devices and equipment
In addition to the current-dependent overload protective device located in the connecting
cables, use the optionally available integrated devices and equipment, for example,
temperature sensor, anti-condensation heating.
Depending on the terminal box version, connect the auxiliary circuits to the terminal block or
to the terminal board.
Terminal block connection
Terminal board connection
Содержание SIMOTICS DP series
Страница 1: ......
Страница 2: ......
Страница 62: ...Assembly 5 4 Installing the machine Standard motors SH 63 355 60 Operating Instructions 12 2018 A5E38483075A ...
Страница 86: ...Commissioning 7 2 Switching on Standard motors SH 63 355 84 Operating Instructions 12 2018 A5E38483075A ...
Страница 98: ...Operation 8 7 Deactivating Standard motors SH 63 355 96 Operating Instructions 12 2018 A5E38483075A ...
Страница 118: ...Maintenance 9 3 Corrective maintenance Standard motors SH 63 355 116 Operating Instructions 12 2018 A5E38483075A ...
Страница 140: ...Disposal 11 6 Disposal of components Standard motors SH 63 355 138 Operating Instructions 12 2018 A5E38483075A ...
Страница 150: ......