Electrical connection
6.2 Connecting the machine
Standard motors SH 63 ... 355
64
Operating Instructions, 12/2018, A5E38483075A
6.2.2.2
Circuit diagram inside the terminal box cover
Data on the connection and connecting the machine winding can be found in the circuit
diagram in the cover of the terminal box.
6.2.2.3
Direction of rotation
The standard motors are suitable for clockwise and counter-clockwise rotation.
For defined directions of rotation (direction of rotation arrow), appropriately connect the line
power cables.
●
If you connect the line cables with phase sequence L1, L2, L3 at U, V, W or according to
NEMA at T
1
T
2
T
3
, then the machine rotates in the clockwise direction.
●
If you interchange two connections, e.g. L1, L2, L3 at V, U, W or according to NEMA at
T
2
T
1
T
3
, then the machine rotates counter-clockwise.
According to IEC
According to NEMA
Clockwise rotation
U V W
T
1
T
2
T
3
Counter-clockwise
rotation
V U W
T
2
T
1
T
3
Direction of rotation of the motor when looking at DE
6.2.2.4
Cable entry
Knockout openings
NOTICE
Damage to the terminal box
To avoid damaging the terminal box:
•
Knockout openings in the terminal box must be knocked out using appropriate methods.
•
Do not damage the terminal box, the terminal board, the cable connections etc. inside
the terminal box.
Содержание SIMOTICS DP series
Страница 1: ......
Страница 2: ......
Страница 62: ...Assembly 5 4 Installing the machine Standard motors SH 63 355 60 Operating Instructions 12 2018 A5E38483075A ...
Страница 86: ...Commissioning 7 2 Switching on Standard motors SH 63 355 84 Operating Instructions 12 2018 A5E38483075A ...
Страница 98: ...Operation 8 7 Deactivating Standard motors SH 63 355 96 Operating Instructions 12 2018 A5E38483075A ...
Страница 118: ...Maintenance 9 3 Corrective maintenance Standard motors SH 63 355 116 Operating Instructions 12 2018 A5E38483075A ...
Страница 140: ...Disposal 11 6 Disposal of components Standard motors SH 63 355 138 Operating Instructions 12 2018 A5E38483075A ...
Страница 150: ......