Maintenance
9.5 Corrective maintenance
Smoke extraction motors
Operating Instructions, 03/2016, 5 610 80000 40 018
77
Replacing bearings
Recommended interval after which bearings are to be replaced under normal operating
conditions:
Table 9- 4
Bearing replacement intervals
Ambient temperature
Principle of operation
Bearing replacement intervals
40 °C
Horizontal coupling operation
40 000 h
40 °C
With axial and radial forces
20 000 h
●
Do not reuse bearings that have been removed.
●
Remove the dirty spent grease from the bearing shield.
●
Replace the existing grease with new grease.
●
Replace the shaft seals when the bearings are replaced.
●
Slightly grease the contact surfaces of the sealing lips.
Note
Special operating conditions
The operating hours are reduced, e.g.
•
When machines are vertically mounted.
•
High vibration and surge loads
•
Frequent reversing operation
•
Higher ambient temperatures.
•
High speeds etc.