Safety and commissioning information for Ex areas
14.2 Dry-running protection for centrifugal pumps by active power monitoring
SIMOCODE pro
System Manual, 05/2019, A5E40507475002A/RS-AD/004
323
The following table shows the test phases performed when the "TEST / RESET" button is
pressed for the required length of time:
Test
phase
Status
Without main current
With main current
OK
Fault *)
OK
Fault
Hardware test / lamp test
< 2 s
"DEVICE" LED
orange
green
orange
green
"GEN.FAULT" LED
Contactor control
Unchanged
Unchanged
Unchanged
Unchanged
Show QL
*)
Results of the hardware test / lamp test
2 - 5 s "DEVICE" LED
green
red
green
red
"GEN.FAULT" LED
Contactor control
Unchanged
Deactivated
Unchanged
Deactivated
Relay test
> 5 s
"DEVICE" LED
green
red
green
red
"GEN.FAULT" LED
Contactor control
Deactivated
Deactivated
Deactivated
Deactivated
LED lights
up / activated
LED flashing
LED flickering
LED off
*) "Fault" only displayed after 2 s
Содержание SIMOCODE pro C
Страница 40: ...Areas of application SIMOCODE pro 40 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Страница 46: ...Features SIMOCODE pro 46 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Страница 64: ...Check list for selecting a device series SIMOCODE pro 64 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Страница 178: ...Accessories SIMOCODE pro 178 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Страница 370: ...CAx data dimension drawings 16 1 CAx data SIMOCODE pro 370 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Страница 374: ...List of abbreviations A 1 List of abbreviations SIMOCODE pro 374 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Страница 398: ...Glossary SIMOCODE pro 398 System Manual 05 2019 A5E40507475002A RS AD 004 ...