Mounting, wiring, connecting, system interfaces, configuration guidelines
12.3 System interfaces
SIMOCODE pro
250
System Manual, 05/2019, A5E40507475002A/RS-AD/004
12.3.8
Modbus RTU connection to the SIMOCODE pro device
Connecting Modbus RTU to the SIMOCODE pro V Modbus basic unit
Modbus RTU can be connected to the SIMOCODE pro V basic unit both via the connecting
terminals as well as via the sub-D connector. The maximum data transfer rate for both
connection methods is 57,600 bps.
NOTICE
9-pin sub-D connection
The 9-way sub-D connection is an alternative to the A/B terminals!
Connecting Modbus RTU to the SIMOCODE pro V Modbus basic unit via the device terminals
Terminal assignment:
Terminal
Modbus signal
A
D0 or DA
B
D1 or DB
SPE
Cable shielding
Connecting Modbus RTU to the SIMOCODE pro V Modbus basic unit via the sub-D connector
The pin assignments of the 9-pin sub-D socket for SIMOCODE pro correspond to the
assignments defined for PROFIBUS DP. The sub-D connector has the following
assignments:
Pin
Modbus signal
8
D0 or DA
3
D1 or DB
5
Cable shielding
Содержание SIMOCODE pro C
Страница 40: ...Areas of application SIMOCODE pro 40 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Страница 46: ...Features SIMOCODE pro 46 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Страница 64: ...Check list for selecting a device series SIMOCODE pro 64 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Страница 178: ...Accessories SIMOCODE pro 178 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Страница 370: ...CAx data dimension drawings 16 1 CAx data SIMOCODE pro 370 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Страница 374: ...List of abbreviations A 1 List of abbreviations SIMOCODE pro 374 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Страница 398: ...Glossary SIMOCODE pro 398 System Manual 05 2019 A5E40507475002A RS AD 004 ...