![Siemens SIMOCODE pro C Скачать руководство пользователя страница 234](http://html.mh-extra.com/html/siemens/simocode-pro-c/simocode-pro-c_system-manual_1265400234.webp)
Mounting, wiring, connecting, system interfaces, configuration guidelines
12.2 Wiring, connecting
SIMOCODE pro
234
System Manual, 05/2019, A5E40507475002A/RS-AD/004
Requirements for an interposing current transformer
●
Secondary current: 1 A
●
Frequency: 50 Hz/60 Hz
●
Transformer rating: Recommended
≥
2.5 VA, depending on the secondary current and
cable length
●
Overcurrent factor: 5P10 or 10P10
●
Accuracy class: 1
Example 1
●
3UF1868-3GA00 current transformer:
–
Primary current: 820 A at nominal load
–
Secondary current: 1 A
●
SIMOCODE pro with 3UF7100-1AA00-0 current measuring module, current setting
0.3 A to 3 A. This means:
–
The secondary current of the current transformer is 1 A at rated load and is, therefore,
within the 0.3 to 3 A setting range of the current measuring module used
–
The current setting I
s
to be parameterized in SIMOCODE pro is 1 A.
Figure 12-30 Example (1 of 2) for measuring current with an 3UF18 external current transformer
Содержание SIMOCODE pro C
Страница 40: ...Areas of application SIMOCODE pro 40 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Страница 46: ...Features SIMOCODE pro 46 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Страница 64: ...Check list for selecting a device series SIMOCODE pro 64 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Страница 178: ...Accessories SIMOCODE pro 178 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Страница 370: ...CAx data dimension drawings 16 1 CAx data SIMOCODE pro 370 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Страница 374: ...List of abbreviations A 1 List of abbreviations SIMOCODE pro 374 System Manual 05 2019 A5E40507475002A RS AD 004 ...
Страница 398: ...Glossary SIMOCODE pro 398 System Manual 05 2019 A5E40507475002A RS AD 004 ...