11
1.9
Measured Values
Measured values
Measuring
path
1
Menu
Tolerances
2
Voltage
A-N, B-N,
C-N, (N-G)
d
a
h
±
0.2%
Voltage
A-B, B-C,
C-A,
Σ
3
d
a
h
±
0.2%
Current
A, B, C, N,
Σ
3
d
a
h
±
0.2%
Real power P
+ import, - export
A, B, C,
Σ
d
a
h
±
0.5%
Reactive power Q
+ leading, - lagging
A, B, C,
Σ
d
a
h
±
0.5%
Apparent power S
A, B, C,
Σ
d
a
h
±
0.5%
Power factor |cos
φ
|
4
A, B, C,
Σ
d
a
h
±
0.5%
Active power factor
cos
φ
4
A, B, C,
Σ
d
a
h
±
0.5%
Phase angle
4
A, B, C,
Σ
d
a
h
±
2°
Frequency
5
A-N
d
a
h
±
10 mHz
Real power import
A, B, C,
Σ
d
a
±
0.5%
Real power export
A, B, C,
Σ
d
a
±
0.5%
Real power absolute
A, B, C,
Σ
d
a
±
0.5%
Real power net
Σ
d
a
±
0.5%
Reactive power leading
A, B, C,
Σ
d
a
±
0.5%
Reactive power lagging
A, B, C,
Σ
d
a
±
0.5%