8
1.7
Mode of Operation
Input voltages and currents are sampled for calculation of
the corresponding r.m.s. values. All measurements derived
from sampled values are calculated by a processor.
Measured quantities can be displayed on the screens and/or
transmitted via the serial interface.
With the SIMEAS P, it is possible to program limit value
groups for various measured quantities to activate limit
violations when the value of a specific measured quantity
exceeds a programmed threshold. In addition, it is possible
use logical elements (AND, OR, etc.) to combine two or
more measured quantities for the purpose of generating a
limit violation. Limit violations are counted, indicated on the
screen and/or utilized to operate the binary output contacts.
The oscilloscope may be triggered via a limit violation as
well.
All measured quantities can be displayed on the
SIMEAS P screens as required by the user. Up to 20
screens can be selected with the front keys. The number,
type, content and sequence of the screens are configurable.
SIMEAS P is delivered with pre-programmed default
settings.
A status line displayed in the measured value screens
indicates status, interfacing and diagnostic messages for
the SIMEAS P.
The display is automatically refreshed every second.
Содержание SIMEAS P 7KG7550
Страница 11: ...9 1 8 Block Diagram Basic device The housing of the RS 485 interface is connected with protective ground PG ...
Страница 22: ...20 1 12 Dimensions IP41 Front NOTE All dimensions are in mm Battery slot Width of the device 144 mm ...
Страница 23: ...21 ...
Страница 24: ...22 IP54 Front NOTE All dimensions in mm Width of the device 144 mm ...
Страница 51: ...49 Notes ...