64
Measured values
Measuring
path
1
Menu
Tolerances
2
Reactive power absolute L1, L2, L3,
Σ
d
a
±
0.5%
Apparent power
L1, L2, L3,
Σ
d
a
±
0.5%
Unbalance voltage
Four-wire
system
d
a
h
±
0.5%
Unbalance current
Four-wire
system
d
a
h
±
0.5%
THD voltage
L1, L2, L3
d
a
h
±
0.5%
THD current
L1, L2, L3
d
a
h
±
0.5%
Harmonic voltage U
5. 7. 11. 13. 17. 19. H.
L1, L2, L3
d
a
h
±
0.5%
Harmonic current I
5. 7. 11. 13. 17. 19. H.
L1, L2, L3
d
a
h
±
0.5%
Limit violations
counter 1
to 4
d
a
Analog inputs
6
external
d
a
±
0.5%
Binary inputs
6
external
d
a
1) Phases are displayed based on the type of connection.
2) Tolerances are applicable from 0.5 to 1.2 times nominal value.
3) Average value of all phases.
4) Measuring beginning with 2% of the internal apparent power
5) Measuring beginning with 30% of the input voltage L1-N
6) 7KG7610 only
d
Measured values can be displayed on measured value
screens (only 7KG7500 and 7KG7600)
a
Measured values selectable over communication
h
Measured values selectable for list screens and oscilloscope
(only 7KG7500 and 7KG7600)
Содержание SIMEAS P 7KG7100
Страница 12: ...9 1 7 Prinzipschaltbild Basisgerät Das Gehäuse der RS485 Schnittstelle ist mit dem Schutzleiter PE verbunden ...
Страница 26: ...23 1 11 2 Gerätevarianten 7KG7500 7KG7600 und 7KG7610 Hinweis Alle Maße in mm Breite des Gerätes 144 mm ...
Страница 32: ...29 1 12 3 Gerätevariante 7KG7610 Achtung Erdung muss an SIMEAS P immer angeschlossen sein V ...
Страница 41: ...38 Einphasen Wechselstrom Dreileiter Drehstrom gleiche Belastung ...
Страница 42: ...39 Dreileiter Drehstrom beliebige Belastung Vierleiter Drehstrom gleiche Belastung ...
Страница 55: ...52 Notizen ...
Страница 64: ...61 2 7 Block Diagram Basic device The housing of the RS 485 interface is connected with protective ground PG ...
Страница 76: ...73 2 11 Dimensions NOTE All dimensions in mm 2 11 1 For Devices 7KG7100 and 7KG7200 Width of the device 94 mm ...
Страница 78: ...75 2 11 2 For Devices 7KG7500 7KG7600 and 7KG7610 NOTE All dimensions in mm Width of the device 144 mm ...
Страница 84: ...81 2 12 3 For Devices 7KG7610 Attention Ground needs to be connected to the SIMEAS P prior operation V ...
Страница 93: ...90 Single phase AC current Three wire three phase balanced ...
Страница 94: ...91 Three wire three phase unbalanced Four wire three phase balanced ...
Страница 95: ...92 Four wire three phase unbalanced low voltage system Four wire three phase unbalanced high voltage system ...
Страница 107: ...104 Notes ...