60
2.6
Mode of Operation
Input voltages and currents are sampled for calculation of
the corresponding r.m.s. values. All measurements derived
from sampled values are calculated by a processor.
Measured quantities can be displayed on the screens and/or
transmitted via the serial interface.
They can be displayed on the screens (only 7KG7500,
7KG7600, and 7KG7610) and/or transmitted via the serial
interface.
With the SIMEAS P, it is possible to program limit value
groups for various measured quantities to activate limit
violations when the value of a specific measured quantity
exceeds a programmed threshold. In addition, it is possible
use logical elements (AND, OR, etc.) to combine two or
more measured quantities for the purpose of generating a
limit violation. Limit violations are counted, indicated on the
screen and/or utilized to operate the binary output contacts.
The oscilloscope may be triggered via a limit violation as
well.
Devices 7KG7500, 7KG7600, and 7KG7610:
All measured quantities can be displayed on the
SIMEAS P screens as required by the user. Up to 20
screens can be selected with the front keys. The number,
type, content and sequence of the screens are configurable.
SIMEAS P is delivered with pre-programmed default
settings.
A status line displayed in the measured value screens
indicates status, interfacing and diagnostic messages for
the SIMEAS P.
The display is automatically refreshed every second.
Содержание SIMEAS P 7KG7100
Страница 12: ...9 1 7 Prinzipschaltbild Basisgerät Das Gehäuse der RS485 Schnittstelle ist mit dem Schutzleiter PE verbunden ...
Страница 26: ...23 1 11 2 Gerätevarianten 7KG7500 7KG7600 und 7KG7610 Hinweis Alle Maße in mm Breite des Gerätes 144 mm ...
Страница 32: ...29 1 12 3 Gerätevariante 7KG7610 Achtung Erdung muss an SIMEAS P immer angeschlossen sein V ...
Страница 41: ...38 Einphasen Wechselstrom Dreileiter Drehstrom gleiche Belastung ...
Страница 42: ...39 Dreileiter Drehstrom beliebige Belastung Vierleiter Drehstrom gleiche Belastung ...
Страница 55: ...52 Notizen ...
Страница 64: ...61 2 7 Block Diagram Basic device The housing of the RS 485 interface is connected with protective ground PG ...
Страница 76: ...73 2 11 Dimensions NOTE All dimensions in mm 2 11 1 For Devices 7KG7100 and 7KG7200 Width of the device 94 mm ...
Страница 78: ...75 2 11 2 For Devices 7KG7500 7KG7600 and 7KG7610 NOTE All dimensions in mm Width of the device 144 mm ...
Страница 84: ...81 2 12 3 For Devices 7KG7610 Attention Ground needs to be connected to the SIMEAS P prior operation V ...
Страница 93: ...90 Single phase AC current Three wire three phase balanced ...
Страница 94: ...91 Three wire three phase unbalanced Four wire three phase balanced ...
Страница 95: ...92 Four wire three phase unbalanced low voltage system Four wire three phase unbalanced high voltage system ...
Страница 107: ...104 Notes ...