Fail-Safe Electronic Modules
8.3 F -Switch PROFIsafe Digital Electronic Module
ET 200pro Distributed I/O System - Fail-Safe Modules
Operating Instructions, 05/2007, A5E00394073-02
137
Technical Specifications
Insulation tested during type test with
•
Shield and ET 200pro bus connection
370 V AC / 1 min or 520 V DC / 1 min
•
ET 200pro bus connection and I/O
370 V AC / 1 min or 520 V DC / 1 min
•
Shield and I/O (DIs, DOs)
370 V AC / 1 min or 520 V DC / 1 min
•
Between DIs and DOs
370 V AC / 1 min or 520 V DC / 1 min
Current consumption
•
From backplane bus
Max. 40 mA
•
From the electronic supply (without load)
50 mA
•
From load voltage L+ (without load)
Typ. 25 mA
Power loss of module
3 W
Status, Interrupts, Diagnostics
Status displays
•
Inputs
Two-color red/green LED per channel
•
Outputs
Two-color red/green LED per channel
•
Sensor supply
LED VsF and display via channel LEDs of
channel group
Interrupts
•
Diagnostic interrupt
Channel LED red
Diagnostic functions
•
Group fault display
Red LED (SF)
•
Diagnostic information can be read out
Possible
•
I&M functionality *
See "ET 200pro Distributed I/O" Manual
Sensor Supply Outputs
Number of outputs
2
Output voltage
•
Loaded
Min. L+ (-1.5 V)
Output current
•
Rated value
200 mA
•
Permissible range
0 mA to 200 mA
•
Permissible aggregate current of outputs
400 mA
•
Short-circuit protection
Yes, electronic
•
Operating value
4 A to 9 A
Data for Selecting a Sensor **
Input voltage
•
Rated value
24 V DC
•
"1" signal
15 V to 30 V
•
"0" signal
-30 V to 5 V
Input current
•
"1" signal
Typ. 3.5 mA
Input delay
For all inputs together
•
For "0" after "1"
Typ. 3 ms
2.0 ms to 4.5 ms
•
For "1" after "0"
Typ. 3 ms
2.0 ms to 4.5 ms
Содержание SIMATIC