Fail-Safe Electronic Modules
8.3 F -Switch PROFIsafe Digital Electronic Module
ET 200pro Distributed I/O System - Fail-Safe Modules
124
Operating Instructions, 05/2007, A5E00394073-02
Special Features for Fault Detection in Use Case 2.3
The following table presents fault detection according to the sensor supply and the
parameter assignment for the short-circuit test:
Table 8-25 F-Switch PROFIsafe Electronic Module: Fault Detection (Use Case 2.3)
Fault detection in case of ...
Example of Fault
Internal sensor supply
and short-circuit test
enabled
Internal sensor supply
and short-circuit test
disabled
External sensor
supply
Short circuit of DI 0 with DI 1
Yes*
Yes*
Yes*
Short circuit of DI 0 with DI 2
Yes
Yes
Yes
Short circuit of DI 0 with DI 3
Yes*
Yes*
Yes*
P-short circuit of DI 0
Yes*
Yes*
Yes*
M-short circuit of DI 0
Yes*
Yes*
Yes*
Discrepancy error
Yes
Yes
Yes
P-short circuit of sensor
supply
Yes
No
No
M-short circuit of sensor
supply or sensor supply
defective
Yes
Yes
Yes
Short-circuit in sensor supply
at DI 0
Yes*
Yes*
Yes*
Supply voltage fault
Yes
Yes
Yes
*: Fault is detected only in case of signal corruption. That is, the signal read differs from the sensor
signal (discrepancy error). If there is no signal corruption relative to the sensor signal, fault detection
is not possible and is not required from a safety standpoint.