2 Engineering
Securely Connecting RTU3041C to TeleControl Server Basic
Entry ID: 109739240, V3.0, 07/2021
63
©
S
iem
e
n
s A
G
2021
A
ll r
igh
ts
re
se
rv
e
d
9. Open the Data points tab.
10. Set the following settings for the digital input "float (DI0)":
–
Transmission method: (Event (only current values))
–
Trigger: Change
–
Transfer mode: Buffered transfer
11. Set the following settings for the digital input "enableReadFillLevel (DI1)":
–
Transmission method: (Event (only current values))
–
Trigger: Change
–
Transfer mode: Buffered transfer
12. Set the following settings for the digital input "gpsPosition (DM2)":
–
Transmission method: (Event (only current values))
–
Trigger: Change
–
Transfer mode: Buffered transfer
13. Set the following settings for the digital memory bit "critFillLevel (DM1)":
–
Transmission method: (Event (only current values))
–
Trigger: Change
–
Transfer mode: Unsolicited transfer
14. Set the following settings for the analog input "fillLevel (AI0)":
–
Transmission method: (Event (only current values))
–
Trigger: Change
–
Threshold (%): 5.00
–
Transfer mode: Buffered transfer