2 Engineering
Securely Connecting RTU3041C to TeleControl Server Basic
Entry ID: 109739240, V3.0, 07/2021
14
©
S
iem
e
n
s A
G
2021
A
ll r
igh
ts
re
se
rv
e
d
Configure default settings
This section explains how to configure the default settings of the SINEMA Remote
Connect Server.
1. Assign an IP address (in the address range of the server) to your "Engineering
PG/PC" for the configuration of the SINEMA Remote Connect Server
(e.g.,
172.16.1.50
).
2. Connect your "Engineering PG/PC" to the WAN port of the SINEMA Remote
Connect Server.
3. Open the web server of the SINEMA Remote Connect Server using the
IP address that you assigned to the WAN port during installation
(e.g.,
172.16.1.60
).
4. Depending on your browser, you may need to trust a certificate or confirm a
security exception.
5. Log into the web server with your user data.
Note
When you log in for the first time, or after a reset to factory settings, the login
details are set as follows:
•
Name: admin
•
Password: admin
Assign a username and a new password for the administrator.
6. Navigate to "System > Date & Time".
7. Accept the time setting of the PC.
Note
To establish secure communication, it is essential that the current time and date
are set on the SINEMA Remote Connect Server. Otherwise the certificates used
will be interpreted as invalid and secure VPN communication is not possible.
8. Optionally, you can also specify an NTP server in the "NTP" tab.