A-2
PP7, PP17-I, PP17-II Equipment Manual
Release 06/98
PP17-II
PP17-I
PP7
Ambient conditions
Shock loading
Operation
Shipping, storage
15 g/11 msec
25 g/6 msec
Vibration
Operation
Shipping, storage
0.075 mm (10 Hz ... 58 Hz)
1 g (58 Hz ... 500 Hz)
3.5 mm (5 Hz ... 10 Hz)
1 g (10 Hz ... 500 Hz)
Max. pressure difference (front/rear sides)
2hPa
Barometric pressure
Operation
Shipping, storage
706 to1030 hPa
581 to 1030 hPa
The conformity of the product described with the regulations of Directive 89/336 EEC is proved by com-
pliance with the following standards:
Interference immunity EN 50082-1
PP7
PP17-II
PP17-II
Static discharge (contact discharge)
EN 61000-4-2 Class 3
RF irradiation
EN 61000-4-3 Class 3
Pulse modulation
ENV 50204 (900 MHz
"
5 MHz)
RF conduction
ENV 50141 Class 3
Burst interference
ENV 61000-4-4 Class 3
Radio interference EN 50081-2
PP7
PP17-I
PP17-II
RFI suppression
EN 55011 Class A
A.2
Digital inputs and outputs
24 V digital inputs
PP7
PP17-I
PP17-II
Power supply
Rated value
Permissible range
Value at t < 0.5 s
+ 24 V DC
+18.0 ... +30.0 V
35 V
Connectable
Keys, switches
Number of inputs
4
16
Potential isolation from internal circuitry
-