Application planning
6.2 Installation location
SIMATIC PN/CAN LINK
Operating Instructions, 03/2022, A5E39895388-AC
81
Also make sure that a depth of at least 25 mm remains clear between the module front and
the inside of the enclosure / control panel.
Table 6- 1
Device dimensions
PN/CAN LINK dimensions
Width
70 mm
Height
111.5 mm (including overhangs)
Depth
75 mm (including overhangs)
The dimension drawing of the PN/CAN LINK is available in the section Dimension drawing
(Page 160).
NOTICE
Damage due to overheating
You must comply with all the instructions regarding the installation site and mounting
position. Otherwise the device may malfunction or incur permanent damage as a result of
overheating.
Pollution degree
The PN/CAN LINK is designed for pollution degree 2. Pollution degree 2 according to the EN
50178 standard is non-conductive contamination in the normal case which can briefly
become conductive as a result of condensation when the device is not in operation.
Pollution of conductive parts through dust, humidity and air pollution can result in fault
conditions and electrical faults in the PN/CAN LINK.
Degree of protection
The housing of the PN/CAN LINK has degree of protection IP20 according to IEC 60529.
The PN/CAN LINK is also rated as "open type" or "open equipment" according to UL 61010-2-
201 or IEC 61010-2-201.
If the PN/CAN LINK is located in an area in which pollution of conductive parts can occur, the
PN/CAN LINK must be protected by an enclosure with the corresponding degree of protection.
IP54 is a protection class that is generally used for electronic systems in heavily polluted
environments and may be suitable for your application.