Diagnostics
11.2 Diagnostic messages to the S7 controller
SIMATIC PN/CAN LINK
148
Operating Instructions, 03/2022, A5E39895388-AC
Mode
Module / submodule
for which the
diagnostic information
is signaled
Channel diagnostics error
Cause of error and possible solution
Manager
Node
Error when starting -
Different product code (OD
1018.2)
The product code ({1:x}) of the node differs
from the configured product code.
Check whether the correct device is connected
and the right EDS file was loaded. If the
product code is 0, the code could not be read
by the device.
Manager
Node
Error when starting -
Different version number
(OD 1018.3)
The version number ({1:d}.{2:d}) of the node
differs from the configured version number.
Check whether the correct device is connected
and the right EDS file was loaded. If the version
number is 0, it could not be read by the device.
Manager
Node
Error when starting -
Writing of the OD
{1:x}:{2:x} was rejected by
the node.
An "SDO abort" message was received.
The exact cause can be determined using a
CAN bus analyzer.
Manager
Node
Error when starting -
Writing of the OD
{1:x}:{2:x} failed.
A timeout has occurred during writing of the
values of OD {1:x}:{2:x}.
Manager
Node
EMCY message with error
code {1:x} was received.
Error tab: {2:x}
Note: If too many EMCY messages are received
in too short a time, not all messages are
displayed in the diagnostic message.
Transparent
Rx message
Received CAN message with
ID {1:x} has incorrect
length.
The received CAN message with {1:x} has a
different length than the configured length
and is therefore discarded.
Correct the configured length.
Manager,
Slave,
Transparent
PROFINET interface
Internal software error -
({1:x}).
An internal error was detected and is now
being signaled after restart of the module.
The error message disappears when you restart
the module again.
Содержание SIMATIC PN/CAN LINK
Страница 1: ......