8
8-14
PG 720 Programming Device
C79000-G7076-C720-02
Using the standard connecting cable (supplied with the unit) you can connect
your PG 720 to a Siemens programmable logic controller. Please refer to the
information in Chapter 3.
PG 7xx
25-pin male connector
activated
Connecting cable
6ES5 734-2BD20
(supplied with PG)
PLC
15-pin male connector
deactivated
19
18
21
19
9
2
6
330 ohms
330 ohms
9
10
7
8
1
1
3
20
Casing
Shield/
casing
+U
–U
+U
–U
Figure 8-10
Standard Connecting Cable
If you want to connect your PG 720 to a PLC using the standard connecting
cable of a PG 6xx, please use an adapter.
PG 7xx
25-pin male
activated
Adapter
6ES5 731-6AG00
(Release 2)
Connecting cable
6ES5 731-1xxx0
PLC
15-pin male
deactivated
330 ohms
330 ohms
19
18
21
22
10
9
2
19
8
6
7
21
9
10
24
25
12
23
20
6
2
3
4
17
8
1
1
3
20
Casing
Shield
Casing
+U
–U
+U
–U
Figure 8-11
Adapter for PG 6xx Cable
Standard
Connecting Cable
Adapter for
PG 6xx Cable
Hardware Information
Содержание SIMATIC PG 720
Страница 32: ...3 3 18 PG 720 Programming Device C79000 G7076 C720 02 Getting to Know the PG 720 ...
Страница 56: ...4 4 24 PG 720 Programming Device C79000 G7076 C720 02 Installing the PG 720 ...
Страница 76: ...6 6 10 PG 720 Programming Device C79000 G7076 C720 02 Configuring the Programming Device ...
Страница 80: ...7 7 4 PG 720 Programming Device C79000 G7076 C720 02 Error Diagnostics ...