The meanings of the fault LED display are as follows:
LED color
LED status
Meaning
Yellow
Lit
The LED can only adopt this status with FM devices.
Check the received power or the loss of power on optical connections. If necessary,
replace the parts.
Red
Lit
The fault LED lighting up can have the following meanings:
• Link down event on a monitored port
• Loss of the power supply
• C-PLUG error
• Device is in PROFINET mode:
– There is no connection to the controller.
– There is a connection to the controller. A configured diagnostics interrupt is also
pending, for example power fail interrupt, C-PLUG interrupt etc.
• Redundancy manager connected through
• Switchover of standby connection
• A defined value was undershot in a monitored optical connection.
• A loop was detected.
• Device startup. The LED lights up for approximately 20 seconds.
Red
Flashing
Internal error detected. Notify maintenance personnel. If necessary, send the device in
for repair.
-
Off
No error detected.
3.5.4
Redundancy manager LED "RM" (green LED)
The green LED shows the following statuses of the X-200:
LED color
LED status
Meaning
Green
Lit
The device is operating in the role of redundancy manager. The ring is operating free of
errors. The monitoring is enabled.
Green
Flashing
The device is operating in the role of redundancy manager. An interruption was detected
in the ring. The device has switched through.
-
Off
The device is not operating in the role of redundancy manager.
Note
This LED labeled on the device with "RM" has a dual function. The color of the display changes
depending on the function:
• If the LED is lit green, the redundancy manager function is indicated.
• If the LED is lit yellow, the standby function is indicated.
In Web Based Management (WBM), the LED is labeled differently depending on the function:
• The redundancy manager function (as shipped) is labeled "RM".
• The standby function is labeled "SB" in the WBM.
Description of the device
3.5 The LEDs
SCALANCE X-200
32
Operating Instructions, 11/2021, C79000-G8976-C284-15
Содержание SIMATIC NET SCALANCE X-200
Страница 8: ...Introduction SCALANCE X 200 8 Operating Instructions 11 2021 C79000 G8976 C284 15 ...
Страница 12: ...Safety notices SCALANCE X 200 12 Operating Instructions 11 2021 C79000 G8976 C284 15 ...
Страница 18: ...Recommendations on network security SCALANCE X 200 18 Operating Instructions 11 2021 C79000 G8976 C284 15 ...
Страница 56: ...Installation and removal 4 9 Disassembly SCALANCE X 200 56 Operating Instructions 11 2021 C79000 G8976 C284 15 ...
Страница 80: ...Maintenance and cleaning SCALANCE X 200 80 Operating Instructions 11 2021 C79000 G8976 C284 15 ...
Страница 92: ...Technical specifications SCALANCE X 200 92 Operating Instructions 11 2021 C79000 G8976 C284 15 ...
Страница 110: ...Index SCALANCE X 200 110 Operating Instructions 11 2021 C79000 G8976 C284 15 ...