Certification
6.3 EMC and Environmental Type Tests
Test
Description
Test Levels
Severity
Levels
DC Power ports
2 kV
AC Power ports
2 kV
Signal ports
5 kV (Fail-Safe
Relay output)
DC Power ports
5 kV
HV Impulse
AC Power ports
5 kV
Siemens-specified severity levels
IEEE 1613 EMC Type Tests
Note
The RUGGEDCOM MX5000 meets Class 2 requirements for an all-fiber configuration
and Class 1 requirements for copper ports.
Description
Test Levels
Enclosure Contact
+/-2 kV, +/-4 kV, +/- 8 kV
ESD
Enclosure Air
+/-4 kV, +/-8 kV, +/-15 kV
Radiated RFI
Enclosure ports
35 V/m
Signal ports
+/- 4 kV @ 2.5 kHz
DC Power ports
+/- 4 kV
AC Power ports
+/- 4 kV
Fast Transient
Earth ground ports
+/- 4 kV
Signal ports
2.5 kV common mode @1 MHz
DC Power ports
2.5 kV common, 1 kV
differential mode @ 1 MHz
Oscillatory
AC Power ports
2.5 kV common, 1 kV
differential mode @ 1 MHz
Signal ports
5 kV (Fail-Safe Relay output)
DC Power ports
5 kV
HV Impulse
AC Power ports
5 kV
Signal ports
2 kV
DC Power ports
2 kV
Dielectric Strength
AC Power ports
2 kV
Environmental Type Tests
Test
Description
Test Levels
IEC 60068-2-1
Cold Temperature
Test Ad
-40 °C (-40 °F), 16 Hours
IEC 60068-2-2
Dry Heat
Test Bd
85 °C (185 °F), 16 Hours
IEC 60068-2-30
Humidity (Damp
Heat, Cyclic)
Test Db
95% (non-condensing),
55 °C (131 °F), 6 cycles
IEC 60255-21-1
Vibration
2 g @ 10 - 150 Hz
RUGGEDCOM MX5000
Installation Manual, 01/2021, C79000-G8976-1059-13
43