Technical Specifications
5
This section provides important technical specifications related to the device and
available modules.
5.1
Power Supply Specifications
Input Range
Power
Supply Type
Min
Max
Internal
Fuse Rating
Max. Power
Consumption
HI (125/250 VDC)
88 VDC
300 VDC
HI (110/230 VAC)
85 VAC
264 VAC
6.3 A, 250 V(T)
110 W
Power consumption varies based on the device configuration. Each 10/100Base-Tx port consumes
roughly 1 W less than a fiber optic port.
The HI power supply is the same power supply for both AC and DC.
(T) denotes time-delay fuse. Internal fuse is not user-replaceable.
Rating at 85 °C (185 °F) ambient temperature at worst-case load.
5.2
Failsafe Relay Specifications
Maximum Switching Voltage
Rated Switching Current
Isolation
30 VDC
2 A, 60 W
125 VDC
0.24 A, 30 W
125 VAC
0.5 A, 62.5 W
220 VDC
0.24 A, 60 W
250 VAC
0.25 A, 62.5 W
1500 V
rms
for 1 minute
5.3
Operating Environment
The RUGGEDCOM MX5000 is rated to operate under the following environmental
conditions.
Ambient Operating
-40 to 85 °C (-40 to 185 °F)
Ambient Storage
Temperature
-40 to 85 °C (-40 to 185 °F)
Ambient Relative
Humidity
5% to 95%
Maximum Altitude
2000 m (6562 ft)
Measured from a 30 cm (12 in) radius surrounding the center of the enclosure.
RUGGEDCOM MX5000
Installation Manual, 01/2021, C79000-G8976-1059-13
35