Technical specifications
8.2 Electromagnetic compatibility
Basic Panels 2nd Generation
Operating Instructions, 10/2016, A5E33293231-AB
99
8.2
Electromagnetic compatibility
The device is designed for industrial use.
8.2.1
Emitted interference
The device meets the requirements according to EN 61000-6-4. The device corresponds to
limit class A.
Note
The HMI device is not intended for use in residential areas. Operation of an HMI device in
residential areas can have a negative influence on radio/TV reception.
8.2.2
Immunity to interferences
The device meets the requirements according to EN 61000-6-2.
8.3
Mechanical ambient conditions
8.3.1
Transport and storage conditions
The following information is for a device that is transported and stored in its original
packaging.
The device meets the requirements according to IEC 60721-3-2, Class 2M2 with the
following amendments and limitations:
Type of condition
Permitted range
Free fall
≤ 1 m
Vibration to IEC 60068-2-6
5 ... 8.4 Hz, deflection 3.5 mm
8.4 ... 500 Hz, acceleration 1 g
Shock to IEC 60068-2-27
250 m/s
2
, 6 ms, 1000 shocks
8.3.2
Operating Conditions
The following information applies to a device installed according to the specifications in these
operating instructions.
The HMI device is designed for stationary operation in a location protected from the effects
of the weather.
The device meets the requirements according to IEC 60721-3-3, Class 3M3 with the
following amendments and limitations:
Type of condition
Permitted range
Vibration according to IEC 60068-2-6
5 ... 8.4 Hz, deflection 3.5 mm
8.4 ... 200 Hz, acceleration 1 g
Shock according to IEC 60068-2-27
150 m/s
2
, 11 ms, 3 shocks