General Technical Data
Distributed I/O Device ET 200R
6–4
(4)J31069-D0427-U001-A2-7618
Shock during operation
The following table specifies permissible shock during operation. The test was per-
formed in accordance with IEC 60068-2-27.
Shock Duration
Shock Form
Acceleration
Amount
11 msec
Half sine
15 g
3 shocks each in +/- direction in
each of the 3 vertical axes
Climatic ambient conditions
The following climatic ambient conditions apply.
Table 6-1
Ambient conditions
Ambient Condition
Application Area
Remarks
Temperature
From 0 ° to 55 °C
Temperature change 3 K/min
Air pressure
Not tested
Relative humidity
Up to 95%
No condensation
Concentration of -
pollutants
SO
2
: < 0,5 ppm;
rel. humidity < 60%, no condensation
H
2
S: < 0,1 ppm;
rel. humidity < 60%, no condensation
Test:
10 ppm; 4 days
1 ppm; 4 days
6.4
Information on isolation tests, protection class,
protection rating and nominal voltage of the ET 200R
Protection rating, IP65
IP65 protection rating in accordance with IEC 529 for the ET 200R distributed I/O
device
•
Protection against dust and total protection against accidental touch
•
Protection against jet of water from a nozzle directed from all sides at the
housing. The water may not cause damage.
Note
The above protection ratings only apply when the ET 200R is completely closed.
Close all unused plugs with the appropriate protective caps.