SICAM FCG Device
6MD2340
s
Product Information
E50417-X1040-C584-A3, Edition 09.2016
Short-Range Radio Communication
Operating frequency band
2.4 GHz
Maximum transmission rate 250 kbit/s
Environmental Data
Temperature Open type; surrounding
air temperature
Maximum 63
°
C
(131
°
F), normal
operation
Operating temperature
-20
°
C to +70
°
C or
-4
°
F to +158
°
F
Temperature during
transport
-25
°
C to +70
°
C or
-13
°
F to +158
°
F
Temperature during
storage
recommendation
-25
°
C to +70
°
C or
-13
°
F to +158
°
F
+10
°
C to +35
°
C or
+50
°
F to +95
°
F
Maximum temperature
gradient
20 K/h
Air humidity Mean relative air
humidity per year
≤
75 %
Maximum relative air
humidity
95 % 30 days a year
Condensation during
operation
Not permitted
Condensation during
transport and storage
Permitted
General Data
Battery
Type
PANASONIC CR2032 or
VARTA 6032 101 501
Voltage
3 V
Capacity
230 mAh
Typical life
10 years
In operation with continuous
supply voltage
2 months within 10 years in
operation where supply voltage
is not applied continuously
Protection
class
DIN rail side
IP20
Terminal side
(terminals)
IP20
Top side
IP20
Electrical Standards
Standards:
R&TTE Standards:
EN 301 511 V9.0.2
EN 300 328 V1.8.1
EN 301 489 V1.9.2
IEC 61010-1, ed. 3.0
IEEE standard C37.90, see
individual functions
VDE 0435
For more standard, see also
individual functions
Insulation Test
Power supply
Rated voltage: DC 12 or DC 24 V, no
insulation
Ethernet interface
Insulation: SELV
Rated voltage: < DC 50 V, insulation
test voltage: DC
700 V
Rated voltage: < DC 50 V, insulation
test voltage: AC
1500 V
Binary outputs
Insulation: reinforced, CAT III
Rated voltage: 300 V
Insulation test voltage: AC 3.51 kV
Binary inputs
Insulation: reinforced, CAT III
Rated voltage (Block P): 300 V
Rated voltage (Block L): 12 V
Insulation test voltage: AC 3.51 kV
EMC Tests for Immunity (Type Tests)
Standards
IEC 61326-1
VDE 0435
For more standard, see
also individual functions
Radio frequency electromagnetic field,
amplitude-modulated
Class III
IEC 61326-1, IEC 61000-4-3
10 V/m; 80 MHz to
2.7 GHz; 80 % AM; 1 kHz
Radio frequency electromagnetic field,
pulse-modulated
IEC 61326-1, IEC 61000-4-3
Frequency: 900 MHz
Modulation: PM 100 %
Keying frequency:
200 Hz, 50 %
Duty cycle: 50 %
Field: 10 V/m
High energy surge voltages (SURGE),
installation class III
IEC 61326-1, IEC 61000-4-5
Impulse: 1.2
µ
s/50
µ
s
Auxiliary voltage
Cable length between
auxiliary voltage and
SICAM FCG device:
maximum 0.5 m
Binary inputs and relay
outputs
Common mode: 2 kV;
42
Ω
; 0.5
µ
F
Binary inputs
Diff. mode: 1 kV; 42
Ω
;
0.5
µ
F
High frequency on line, amplitude-
modulated, class III
IEC 61326-1, IEC 61000-4-6
10 V; 150 kHz to 80 MHz;
80 % AM; 1 kHz
Power system frequency magnetic field
IEC 61326-1, IEC 61000-4-8, class IV;
30 A/m continuous;
300 A/m for 3 s;
Damped oscillations
IEC 61000-4-18
2.5 kV (peak value);
100 kHz;
40 pulses per s; test
duration 2 s;
Ri = 200
Ω