Siemens SICAM FCG Скачать руководство пользователя страница 6

SICAM FCG Device  

6MD2340

  

 

 

 

                     

       

 

 

 

 

 

Product Information  

E50417-X1040-C584-A3, Edition  09.2016 

 

Short-Range Radio Communication  

Operating frequency band  

2.4 GHz 

Maximum transmission rate   250 kbit/s 

 
Environmental Data  

Temperature    Open type; surrounding 

air temperature 

Maximum 63 

°

C  

(131 

°

F), normal 

operation 

Operating temperature 

-20 

°

C to +70 

°

C or  

-4 

°

F to +158 

°

Temperature during 

transport 

-25 

°

C to +70 

°

C or  

-13 

°

F to +158 

°

Temperature during 

storage 
recommendation 

-25 

°

C to +70 

°

C or  

-13 

°

F to +158 

°

+10 

°

C to +35 

°

C or  

+50 

°

F to +95 

°

Maximum temperature 

gradient 

20 K/h 

 

Air humidity    Mean relative air 

humidity per year 

 

 75 % 

Maximum relative air 

humidity 

95 % 30 days a year 

Condensation during 

operation 

Not permitted 

Condensation during 

transport and storage  

 Permitted 

 
General Data  

Battery  

Type 

 PANASONIC CR2032 or 

VARTA 6032 101 501 

Voltage 

3 V 

Capacity 

230 mAh 

Typical life  

10 years 
In operation with continuous 

supply voltage 

2 months within 10 years in 

operation where supply voltage 

is not applied continuously 

Protection 

class 

DIN rail side 

 IP20 

Terminal side 

(terminals)  

 IP20 

Top side 

 IP20 

 
Electrical Standards  

Standards: 
R&TTE Standards:  
EN 301 511 V9.0.2 
EN 300 328 V1.8.1 
EN 301 489 V1.9.2 

IEC 61010-1, ed. 3.0 
IEEE standard C37.90, see 

individual functions  
VDE 0435  
For more standard, see also 

individual functions 

Insulation Test  

Power supply 

Rated voltage: DC 12 or DC 24 V, no 

insulation 

Ethernet interface 

Insulation: SELV 
Rated voltage: < DC 50 V, insulation 

test voltage: DC

 

700 V 

Rated voltage: < DC 50 V, insulation 

test voltage: AC

 

1500 V 

Binary outputs 

Insulation: reinforced, CAT III 
Rated voltage: 300 V 
Insulation test voltage: AC 3.51 kV 

Binary inputs 

Insulation: reinforced, CAT III 
Rated voltage (Block P): 300 V  
Rated voltage (Block L): 12 V  
Insulation test voltage: AC 3.51 kV 

 
EMC Tests for Immunity (Type Tests) 

Standards 

IEC 61326-1  
VDE 0435  
For more standard, see 

also individual functions 

Radio frequency electromagnetic field, 

amplitude-modulated 
Class III  
IEC 61326-1, IEC 61000-4-3 

10 V/m; 80 MHz to  

2.7 GHz; 80 % AM; 1 kHz 

Radio frequency electromagnetic field, 

pulse-modulated 
IEC 61326-1, IEC 61000-4-3 

Frequency: 900 MHz  
Modulation: PM 100 %  
Keying frequency:  

200 Hz, 50 %  
Duty cycle: 50 %  
Field: 10 V/m 

High energy surge voltages (SURGE), 

installation class III  
IEC 61326-1, IEC 61000-4-5  

Impulse: 1.2 

µ

s/50 

µ

 

Auxiliary voltage 

Cable length between 

auxiliary voltage and 

SICAM FCG device: 

maximum 0.5 m 

Binary inputs and relay 

outputs 

Common mode: 2 kV;  

42 

Ω

; 0.5 

µ

Binary inputs 

Diff. mode: 1 kV; 42 

Ω

0.5 

µ

High frequency on line, amplitude-

modulated, class III 
IEC 61326-1, IEC 61000-4-6 

10 V; 150 kHz to 80 MHz; 

80 % AM; 1 kHz 

Power system frequency magnetic field 
IEC 61326-1, IEC 61000-4-8, class IV; 

30 A/m continuous;  

300 A/m for 3 s; 

Damped oscillations 
IEC 61000-4-18  

2.5 kV (peak value);  

100 kHz; 
40 pulses per s; test 

duration 2 s; 
Ri = 200 

Ω

  

 

Содержание SICAM FCG

Страница 1: ...excluded We do not provide any technical support for the Product if it has been modified Notes on Safety This document contains notes that must be adhered to for your own personal safety and to avoid damage to property However it does not constitute a complete description of all safety measures required for installation service and maintenance of the equipment module device in question Details are...

Страница 2: ...way that meets the requirements of standard ISO 2248 Check the packing for external transport damage Damaged packing may indicate that the devices inside have also sustained damage Unpack devices carefully do not use force Visually check the devices to ensure that they are in perfect mechanical condition Check the enclosed accessories against the delivery note to make sure that everything is compl...

Страница 3: ...ltage and to the maximum values 2 Connect the desired devices to the terminals and plug connectors see figure 1 3 Install the SIM card and connect the GSM antenna according to Device Manual 4 Switch on the connected peripheral devices and the supply voltage of the device NOTE The device does not have a power on off switch Switch on off the supply voltage at the respective isolating device or at th...

Страница 4: ...f the device is stored for an extended period of time Siemens recommend to connect the device to the supply voltage for 1 or 2 days once a year to reform the electrolytic capacitors in the device This procedure should also be carried out before operating the device Transport SICAM FCG with 1 contained lithium metal cell button cell with 0 07 g lithium content meets the preconditions of Special Pro...

Страница 5: ...nsmission rate 10 100 Mbit s Cable for 100Base T 100 Ω to 150 Ω STP CAT5 Maximum cable length 100Base T 100 m if installed GSM Antenna and Antenna Interface Requirements for Antenna Type Fixed antenna For use in industrial environment acc to EN IEC 61010 1 Ed 3 CAT III Detached antenna For remote installation in residential commercial and light industrial environments EN IEC 61010 1 Ed 3 CAT III A...

Страница 6: ...sulation Test Power supply Rated voltage DC 12 or DC 24 V no insulation Ethernet interface Insulation SELV Rated voltage DC 50 V insulation test voltage DC 700 V Rated voltage DC 50 V insulation test voltage AC 1500 V Binary outputs Insulation reinforced CAT III Rated voltage 300 V Insulation test voltage AC 3 51 kV Binary inputs Insulation reinforced CAT III Rated voltage Block P 300 V Rated volt...

Страница 7: ... 5 Hz to 8 Hz 7 5 mm amplitude 8 Hz to 150 Hz 2 g acceleration Frequency sweep 1 octave min 20 cycles in 3 orthogonal axes Shock IEC 62586 1 class 1 IEC 60068 2 27 test Ea Semi sinusoidal 15 g acceleration duration 11 ms Each 3 shocks in both directions of the 3 axes Shock IEC 62586 1 class 1 IEC 60068 2 29 test Eb Semi sinusoidal 10 g acceleration duration 16 ms Each 1000 shocks in both direction...

Страница 8: ...s Product Information E50417 X1040 C584 A3 Edition 09 2016 1 SICAM FCG Terminal Side 2 SICAM FCG DIN Rail Side 3 SICAM FCG Device Top Side Cover of Battery Compartment 4 SICAM FCG DIN rail Assembly 5 SICAM FCG Dimension Drawing ...

Отзывы: