SICAM FCG Device
6MD2340
s
Product Information
E50417-X1040-C584-A3, Edition 09.2016
Structure of the HTML pages
NOTE
Request in accordance with EN 301511:
The Ethernet port must be switched off after putting
into operation and as long as the Ethernet interface is
not needed using the button "IP Addr". The
communication then takes place only via mobile
communication.
Repair
CAUTION
Danger of damage due to static electrical charges
The user is not authorized to repair the device when it is
defective. This is because the device contains special
electronic components that may only be handled by the
manufacturer in compliance with the regulations for
electrostatic sensitive devices (ESD).
Furthermore, hazardous voltages can lead to lethal injuries
when the work is performed improperly.
If you suspect that the device has a defect, Siemens
recommends to send the entire device back to the
manufacturer.
Cleaning
Switch off the device. Wiped the device with a clean, dry and soft cloth. Do
not use solvents.
Repacking a Device
•
If you store devices after incoming inspection, pack them in suitable
storage packaging.
•
If devices are to be transported, pack them in transport packing.
•
Put the accessories supplied and the test certificate in the packing
with the device.
Storage
•
Only store devices on which you have carried out an incoming
inspection, thus ensuring that the warranty remains valid.
•
Store the device in a dry and clean location.
•
The relative air humidity must not lead to condensation or ice
formation.
•
To avoid premature aging of the electrolytic capacitors, store the
device within the recommended temperature range of +10 °C to
+35 °C (+50 °F to +95 °F)
•
If the device is stored for an extended period of time, Siemens
recommend to connect the device to the supply voltage for 1 or 2
days once a year to reform the electrolytic capacitors in the device.
This procedure should also be carried out before operating the
device.
Transport
SICAM FCG with 1 contained lithium metal cell (button cell with 0.07 g
lithium content) meets the preconditions of Special Provision
188
of
the UN Recommendations on the Transport of Dangerous Goods, 17th
revised edition and is classified according to:
• ADR/RID/ADN/IMDG-Code: UN 3091 lithium metal batteries
contained in equipment, 9, preconditions of SP
188
• ICAO-TI/IATA-DGR: UN 3091 lithium metal batteries contained in
equipment, 9, preconditions of
Section II of PI 970
Technical Data
DC 12 or DC 24 V Power Supply
Rated input voltages
DC 12 V or DC 24 V SELV
Input-voltage range
DC 10 V to 28.8 V
Maximum input current
1 A
Power input typical (12 V)
3 W
Maximum power input
4.3 W (typical)
Safety
CAT III
Fixed installation according to IEC
61010-1 ed. 3
Binary Inputs (Terminal Block P)
Number according to device
3
Rated input voltage range
DC 24 V to DC 250 V; AC not
allowed
Threshold voltages (adjustable)
Threshold voltage 19 V
(at rated voltage 24 V)
V high ≥ 19 V
V low ≤ 14 V
Threshold voltage 88 V
(at rated voltage 110 V)
V high ≥ 88 V
V low ≤ 66 V
Threshold voltage 176 V
(at rated voltage 220 V)
V high ≥ 176 V
V low ≤ 132 V
Maximum input voltage
DC 300 V
Binary Inputs (Terminal Block L)
Number according to device
variant
3
Input voltage range
DC 9 V to DC 20 V; AC not
allowed
Rated voltage
12 V
Threshold voltage 7 V
(at rated voltage 12 V)
V high ≥ 10 V
V low ≤ 4 V
Maximum input voltage
DC 20 V
Binary Outputs (Relay Outputs)
Type of relay
NO relay
CO relay
Number
2
1
Output values
Switching capacity
On: 1000 W/VA
Off: 30 VA; 40 W ohmic
25 W/VA at L/R
≤
40 ms
Contact voltage AC and DC
250 V