SICAM FCG Device  

6MD2340

  

 

 

 

                     

       

 

 

 

 

 

Product Information  

E50417-X1040-C584-A3, Edition  09.2016 

 

Structure of the HTML pages 

 

 

 

 

NOTE  

Request in accordance with EN 301511: 
The Ethernet port must be switched off after putting 

into operation and as long as the Ethernet interface is 

not needed using the button "IP Addr". The 

communication then takes place only via mobile 

communication. 

 
Repair 

 

CAUTION

 

Danger of damage due to static electrical charges 

The user is not authorized to repair the device when it is 

defective. This is because the device contains special 

electronic components that may only be handled by the 

manufacturer in compliance with the regulations for 

electrostatic sensitive devices (ESD). 
Furthermore, hazardous voltages can lead to lethal injuries 

when the work is performed improperly. 
If you suspect that the device has a defect, Siemens 

recommends to send the entire device back to the 

manufacturer. 

Cleaning 

Switch off the device. Wiped the device with a clean, dry and soft cloth. Do 

not use solvents.

 

 

Repacking a Device  

 

If you store devices after incoming inspection, pack them in suitable 

storage packaging. 

 

If devices are to be transported, pack them in transport packing.  

 

Put the accessories supplied and the test certificate in the packing 

with the device.  

Storage 

 

Only store devices on which you have carried out an incoming 

inspection, thus ensuring that the warranty remains valid.  

 

Store the device in a dry and clean location. 

 

The relative air humidity must not lead to condensation or ice 

formation. 

 

To avoid premature aging of the electrolytic capacitors, store the 

device within the recommended temperature range of +10 °C to  

+35 °C (+50 °F to +95 °F) 

 

If the device is stored for an extended period of time, Siemens 

recommend to connect the device to the supply voltage for 1 or 2 

days once a year to reform the electrolytic capacitors in the device. 

This procedure should also be carried out before operating the 

device.

 

Transport 

SICAM FCG with 1 contained lithium metal cell (button cell with 0.07 g  

     lithium content) meets the preconditions of Special Provision 

188

 of  

     the UN Recommendations on the Transport of Dangerous Goods, 17th  

     revised edition and is classified according to:

 

•  ADR/RID/ADN/IMDG-Code: UN 3091 lithium metal batteries  

       contained in equipment, 9, preconditions of SP 

188

  

•  ICAO-TI/IATA-DGR: UN 3091 lithium metal batteries contained in  

       equipment, 9, preconditions of 

Section II of PI 970

  

 

 

Technical Data  
DC 12 or DC 24 V Power Supply 

Rated input voltages 

DC 12 V or DC 24 V SELV 

Input-voltage range 

DC 10 V to 28.8 V 

Maximum input current 

1 A 

Power input typical (12 V) 

3  W 

Maximum power input 

4.3 W (typical) 

Safety 

CAT III 
Fixed installation according to IEC 

61010-1 ed. 3 

 

Binary Inputs (Terminal Block P) 

Number according to device 

3  

Rated input voltage range 

DC 24 V to DC 250 V; AC not 

allowed 

Threshold voltages (adjustable) 

Threshold voltage 19 V  
(at rated voltage 24 V) 

V high ≥ 19 V 
V low ≤ 14 V 

Threshold voltage 88 V  
(at rated voltage 110 V) 

V high ≥ 88 V 
V low ≤ 66 V 

Threshold voltage 176 V  
(at rated voltage 220 V) 

V high ≥ 176 V 
V low ≤ 132 V 

Maximum input voltage 

DC 300 V 

 

Binary Inputs (Terminal Block L) 

Number according to device 

variant 

3  

Input voltage range 

DC 9 V to DC 20 V; AC not 

allowed 

Rated voltage  

12 V 

Threshold voltage 7 V  
(at rated voltage 12 V) 

V high ≥ 10 V 
V low ≤ 4 V 

Maximum input voltage 

DC 20 V 

 
Binary Outputs (Relay Outputs)  

Type of relay 

NO relay 

CO relay 

Number 

Output values 

 

Switching capacity 

On: 1000 W/VA 
Off: 30 VA; 40 W ohmic 
25 W/VA at L/R 

 40 ms 

Contact voltage AC and DC 

250 V 

Содержание SICAM FCG

Страница 1: ...excluded We do not provide any technical support for the Product if it has been modified Notes on Safety This document contains notes that must be adhered to for your own personal safety and to avoid damage to property However it does not constitute a complete description of all safety measures required for installation service and maintenance of the equipment module device in question Details are...

Страница 2: ...way that meets the requirements of standard ISO 2248 Check the packing for external transport damage Damaged packing may indicate that the devices inside have also sustained damage Unpack devices carefully do not use force Visually check the devices to ensure that they are in perfect mechanical condition Check the enclosed accessories against the delivery note to make sure that everything is compl...

Страница 3: ...ltage and to the maximum values 2 Connect the desired devices to the terminals and plug connectors see figure 1 3 Install the SIM card and connect the GSM antenna according to Device Manual 4 Switch on the connected peripheral devices and the supply voltage of the device NOTE The device does not have a power on off switch Switch on off the supply voltage at the respective isolating device or at th...

Страница 4: ...f the device is stored for an extended period of time Siemens recommend to connect the device to the supply voltage for 1 or 2 days once a year to reform the electrolytic capacitors in the device This procedure should also be carried out before operating the device Transport SICAM FCG with 1 contained lithium metal cell button cell with 0 07 g lithium content meets the preconditions of Special Pro...

Страница 5: ...nsmission rate 10 100 Mbit s Cable for 100Base T 100 Ω to 150 Ω STP CAT5 Maximum cable length 100Base T 100 m if installed GSM Antenna and Antenna Interface Requirements for Antenna Type Fixed antenna For use in industrial environment acc to EN IEC 61010 1 Ed 3 CAT III Detached antenna For remote installation in residential commercial and light industrial environments EN IEC 61010 1 Ed 3 CAT III A...

Страница 6: ...sulation Test Power supply Rated voltage DC 12 or DC 24 V no insulation Ethernet interface Insulation SELV Rated voltage DC 50 V insulation test voltage DC 700 V Rated voltage DC 50 V insulation test voltage AC 1500 V Binary outputs Insulation reinforced CAT III Rated voltage 300 V Insulation test voltage AC 3 51 kV Binary inputs Insulation reinforced CAT III Rated voltage Block P 300 V Rated volt...

Страница 7: ... 5 Hz to 8 Hz 7 5 mm amplitude 8 Hz to 150 Hz 2 g acceleration Frequency sweep 1 octave min 20 cycles in 3 orthogonal axes Shock IEC 62586 1 class 1 IEC 60068 2 27 test Ea Semi sinusoidal 15 g acceleration duration 11 ms Each 3 shocks in both directions of the 3 axes Shock IEC 62586 1 class 1 IEC 60068 2 29 test Eb Semi sinusoidal 10 g acceleration duration 16 ms Each 1000 shocks in both direction...

Страница 8: ...s Product Information E50417 X1040 C584 A3 Edition 09 2016 1 SICAM FCG Terminal Side 2 SICAM FCG DIN Rail Side 3 SICAM FCG Device Top Side Cover of Battery Compartment 4 SICAM FCG DIN rail Assembly 5 SICAM FCG Dimension Drawing ...