SICAM FCG Device
6MD2340
s
Product Information
E50417-X1040-C584-A3, Edition 09.2016
Application
This product information refers to the SICAM FCG device provided for the
various applications in power supply companies and at consumers:
•
Transmits the load current values and distribution line faults status
and events to the SCADA control center based on the
IEC 60870-5-104 protocol.
SICAM FCG transmits the distribution line fault status and events to the
cloud based fault location service "FLiC" based on the XMPP protocol.
A mobile communication interface is provided.
Parameterization via HTML pages using a web browser is supported by
a web server that is integrated in the device.
For parameterization via HTML pages, an Ethernet interface is provided.
The mobile interface can be used alternatively once the mobile
connection has been set up.
The respective device manual contains more detailed information, for
example, on the following topics:
user information, device versions, ordering information, device design
(mechanical, electrical), installation and commissioning, interfaces,
connection types, parameterization and operation via HTML pages,
operating parameters, time synchronization, maintenance, malfunctions,
operational indications and error messages, detailed technical data.
Mounting, Commissioning, and Connection Types of the Device
WARNING
Danger of death, personal injury or substantial
property damage
Non-observance of the following measures can result in
death, personal injury or substantial property damage.
•
Work may only be carried out by trained personnel
who are familiar with and observe the safety
requirements and precautions.
•
When performing electrical installations, you have to
observe the national and international regulations on
the erection of electrical power installations.
•
Work may never be carried out if there is any
dangerous voltage present.
•
De-energize the device.
Connect the protective conductor terminals L and P
to the protective conductor of the switch panel or of
the control cabinet.
•
All circuit components connected to the power supply
may be subject to dangerous voltage.
•
Hazardous voltages may be present in equipment
even after the supply voltage has been disconnected
(capacitors can still be charged).
•
The limit values stated under “Technical Data” in the
corresponding device manual may not be exceeded.
This must also be considered during testing and
commissioning.
Unpacking a Device
Devices are tested prior to delivery. Devices are packed on site in a way
that meets the requirements of standard ISO 2248.
•
Check the packing for external transport damage. Damaged packing
may indicate that the devices inside have also sustained damage.
•
Unpack devices carefully; do not use force.
•
Visually check the devices to ensure that they are in perfect
mechanical condition.
•
Check the enclosed accessories against the delivery note to make sure
that everything is complete.
•
Keep the packing in case the devices must be stored or transported
elsewhere.
•
Return damaged devices to the manufacturer, stating the defect.
NOTE
Before commissioning the device, leave it in the final
operating room for at least 2 hours. This allows it to
reach room temperature and to prevent dampness and
condensation.
Mounting
General Information
1. Before installing the device, insert the supplied Lithium battery
(see below).
2. The device should be mounted in a dry, dirt free location.
3. Keep a minimum distance of 10.5 mm to adjacent devices.
4. Field Wires of Control Circuits shall be separated from other circuits
with respect to the end use requirements!
5. The permitted ambient temperature must be observed (see technical
data). Operating the device outside the permitted operating
temperature range can lead to measuring errors and device failure.
6. The terminals are designed for conductor cross-sections of 2.5 mm²
max. (AWG 14).
7. During operation, the device must not be exposed to condensation,
direct sunlight, or extreme temperature changes.
8. The above mounting instructions must be performed correctly to
provide sufficient protection against touching live parts.
Lithium Battery
CAUTION
Danger of fire or chemical burn hazard
The battery used in this device may present a fire or
chemical burn hazard if mistreated.
•
Batteries must only be replaced with the same type or
the types recommended by Siemens, PANASONIC
CR2032 or VARTA 6032 101 501.
•
Do not reverse the polarity of the battery.
•
Do not recharge, disassemble, heat above 100 °C
(212 °F) or incinerate.
•
Dispose the used battery promptly.
•
Keep away from children!
First installation / replacement of the lithium battery
The delivery includes a lithium battery that powers the battery-buffered
memory and the real-time clock. Upon delivery, the battery is insulated
with a plastic foil in the battery compartment of the device.
Replace the battery if the battery charge is too low (operational indication
"Battery Failure".
Proceed as follows for the first installation or for battery replacement:
1. Lever the cover of the battery compartment out of the socket
with a suitable tool (e.g. precision engineer screwdriver 2.0 mm), see
figure 3.
2. Take the battery out of the battery compartment and - in case of first
installation remove the plastic foil.