Document No. 129-479 
Installation Instructions 
November 13, 2012 

2300

DC+ ACH

DC- ACN (GND)

Signal Out

CONTROLLER

Sensor Power DC
Common
Signal In

Common

Signal In

SEN0652R1

Isolated DC

Supply 300 MA Max.

I
I
I
I
I

DC+

DC-

AC

IN

Powered By

Controller

See Controller

Installation Instructions

For Power Input

Requirements

2300

DC+ ACH

DC- ACN (GND)

Signal Out

Powered By

Isolated DC

 

NOTE: 

 

 
Externally DC powered 
2300 Room Units 
require isolated DC 
supply with all 
commons connected 
and may be used on 
the same controller 
with other Room Units 
powered by internal 
sensor supply. 

Figure 8.  Externally DC Powered 2300 Room Units. 

2300

DC+ ACH

DC- ACN (GND)

Signal Out

CONTROLLER

Sensor Power DC
Common
Signal In

Common
Signal In
Common
Signal In
Common

Common

Signal In

SEN0651R1

Class 2

Isolated AC Supply

100 VA Max.

Powered By

Class 2 (100VA)

Isolated AC

I
I
I
I
I

I
I
I
I
I

ACH
ACN

ACH
ACN

ACH
ACN

Powered By

Controller

2300

DC+ ACH

DC- ACN (GND)

Signal Out

2300

100 VA

DC+ ACH
DC- ACN (GND)
Signal Out

Powered By

Class 2 (100VA)

Isolated AC

L    N    E

With Class 2 (100 VA) Output

Isolated AC Supply

(See Controller

Installation Instructions)

L   N   E

Note: See Caution

 

NOTE:

 

 
Externally AC powered 
2300 Room Units require 
controller common and all 
AC secondary neutral ACN 
to be earth grounded and 
may be used on the same 
controller with other room 
units powered by internal 
sensor supply. 

Figure 9.  Externally AC Powered 2300 Room Units. 

 

Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as 
design improvements are introduced. TALON and Predator are registered trademarks of Siemens Industry, Inc. Other product or company names 
mentioned herein may be the trademarks of their respective owners. © 2012 Siemens Industry, Inc. 

 

Siemens Industry, Inc. 

Building Technologies Division 
1000 Deerfield Parkway 
Buffalo Grove, IL 60089 
USA 
+ 1 847-215-1000 

Your feedback is important to us. If you have 
comments about this document, please send them to 

[email protected]

 

 

Document No. 129-479 

Printed in the USA 

Page 6 of 6

 

Содержание Series 2300

Страница 1: ...QAA2330 xWxx QAA23SS xWxN QAA23SS xWxx Accessories AQA2200 INTL Room Unit Back Plate 10 pack AQA2200 2X4 Room Unit Back Plate Single NOTE If installing the Back Plate discard the metric screws provided with the Back Plate and utilize the Room Unit mounting screws Caution Notations CAUTION Equipment damage or loss of data may occur if you do not follow a procedure as specified Expected Installation...

Страница 2: ...o plastic wall anchors flush to below the wall surface for stable mounting of the device 3 Cut a 1 inch 25 mm center hole with a hole saw 4 Pull about three inches 75 mm of the cable through the hole in the base plate 5 Mount the room unit base plate on the wall noting the UP arrow NOTE If required position the Back Plate behind the Room Unit Base aligning the top and bottom mounting holes prior t...

Страница 3: ... locator by removing the two screws and lightly rocking the locator to pull it free 2 Untie the twist tie and pull about three inches 75 mm of the room unit cable through the hole in the base plate 3 Mount the room unit base plate on the wall noting the UP arrow NOTE If required position the Back Plate behind the Room Unit Base aligning the top and bottom mounting holes prior to mounting to the wa...

Страница 4: ...or Controller a 500 ohm resistor must be wired in series with the setpoint termination on the Predator Controller and the Override termination 8 on the Room Sensor See Figure 6 and Figure 7 for the complete wiring diagrams for the two different style controllers The installation is now complete 1 2 3 4 5 6 7 8 9 10 11 12 SEN0485R1 Figure 5 Typical Wiring Base All terminals may not be present Pin N...

Страница 5: ...0644R1 500 ohm Orange White Orange White Green White Blue Blue Green 5 SetPoint Bypass 6 Room Temp 2 LonNetwork 4 Common 3 Service Pin LCD Power 1 LonNetwork Color Pin Wire Twisted Pair Twisted Pair Twisted Pair P I 9 11 Figure 7 Pin No Function QAA2312 EWTN 2 Temperature 3 Temp_Common QAA2330 EWxC 2 Temperature 3 Temp_Common 7 LON1 8 LON2 QAA23SS EWxN 1 DC or ACH 2 DC or ACN GND 3 Temperature Out...

Страница 6: ...300 100 VA DC ACH DC ACN GND Signal Out Powered By Class 2 100VA Isolated AC L N E With Class 2 100 VA Output Isolated AC Supply See Controller Installation Instructions L N E Note See Caution NOTE Externally AC powered 2300 Room Units require controller common and all AC secondary neutral ACN to be earth grounded and may be used on the same controller with other room units powered by internal sen...

Отзывы: