Installation Instructions 

November 13, 2012 

1. 

If the device has a switch, determine if voltage 
or current output is needed. 

 

For current, set the switch in the down 
position (I). 

 

For voltage, set the switch in the up position 
(V). 

NOTE: 

The output setting applies to all 
outputs (temperature, and setpoint). 

2.  If selecting voltage, set the jumper: 

 

Use the top and middle pins for 0-5V. 

 

Use the bottom and middle pins for 0-10V. 

NOTE: 

If the jumper is missing or removed, 
the output voltage will default to  
0-10V. 

NOTE: 

The factory default for displayed 
temperature units is °F. To change the 
display to °C, snip the wire jumper (0 Ohm 
resistor R64) on the back of the PCA. 

SEN0588R1

°

F

°

C

 

Figure 4.  Changing Display to °C. 

9.  Snap the room unit cover to the room unit base 

plate by first hooking the room unit front to the 
top latches, and then rotating the cover 
downward until it latches. 

10.  Loosen the safety set screw at the bottom of the 

base one or two revolutions to lock the cover to 
the base. Be careful not to loosen too far as the 
screw can be completely removed from the 
base. 

Electrical Box and Rough-in 
Mounting, Typical 

1. 

If a locator is attached to the rough-in device, 
remove the locator by removing the two screws 
and lightly rocking the locator to pull it free. 

2. 

Untie the twist tie and pull about three inches 
(75 mm) of the room unit cable through the hole 
in the base plate. 

3.  Mount the room unit base plate on the wall, 

noting the UP arrow: 

NOTE: 

If required, position the Back Plate 
behind the Room Unit Base, aligning 
the top and bottom mounting holes, 
prior to mounting to the wall: 

a.  Install the two room unit mounting screws 

provided, but do not tighten. 

b.    Level the room unit base plate for 

appearance only. 

c.  Tighten the two mounting screws to the 

room unit base plate. 

CAUTION: 

 

Over-tightening may cause the room unit 
base plate to crack or bend. 

4. Continue 

with 

Drywall Mounting (No Rough-in), 

Typical

, Steps 6 through 8, and 

Sensor Set-up

CAUTION: 

 

To prevent equipment damage, do the 
following:  

If room unit is powered by AC (See Figure 
9): 

  AC Supply must be type NEC Class 2 and 

earth grounded at the secondary neutral. 

  Room Unit ACN (GND) must be 

connected to the controller common. 

  If the controller has a floating common, 

that common must be connected to the 
same earth ground point as the controller 
AC supply. 

If room unit is powered by isolated DC 
(See Figure 8): 

  Where power is current limited up to 300 

mA, it is not required to earth ground the 
controller isolated common. 

  Room Unit DC-(GND) must be 

connected to the controller common. 

Siemens Industry, Inc. 

Page 3 of 6

 

Содержание Series 2300

Страница 1: ...QAA2330 xWxx QAA23SS xWxN QAA23SS xWxx Accessories AQA2200 INTL Room Unit Back Plate 10 pack AQA2200 2X4 Room Unit Back Plate Single NOTE If installing the Back Plate discard the metric screws provided with the Back Plate and utilize the Room Unit mounting screws Caution Notations CAUTION Equipment damage or loss of data may occur if you do not follow a procedure as specified Expected Installation...

Страница 2: ...o plastic wall anchors flush to below the wall surface for stable mounting of the device 3 Cut a 1 inch 25 mm center hole with a hole saw 4 Pull about three inches 75 mm of the cable through the hole in the base plate 5 Mount the room unit base plate on the wall noting the UP arrow NOTE If required position the Back Plate behind the Room Unit Base aligning the top and bottom mounting holes prior t...

Страница 3: ... locator by removing the two screws and lightly rocking the locator to pull it free 2 Untie the twist tie and pull about three inches 75 mm of the room unit cable through the hole in the base plate 3 Mount the room unit base plate on the wall noting the UP arrow NOTE If required position the Back Plate behind the Room Unit Base aligning the top and bottom mounting holes prior to mounting to the wa...

Страница 4: ...or Controller a 500 ohm resistor must be wired in series with the setpoint termination on the Predator Controller and the Override termination 8 on the Room Sensor See Figure 6 and Figure 7 for the complete wiring diagrams for the two different style controllers The installation is now complete 1 2 3 4 5 6 7 8 9 10 11 12 SEN0485R1 Figure 5 Typical Wiring Base All terminals may not be present Pin N...

Страница 5: ...0644R1 500 ohm Orange White Orange White Green White Blue Blue Green 5 SetPoint Bypass 6 Room Temp 2 LonNetwork 4 Common 3 Service Pin LCD Power 1 LonNetwork Color Pin Wire Twisted Pair Twisted Pair Twisted Pair P I 9 11 Figure 7 Pin No Function QAA2312 EWTN 2 Temperature 3 Temp_Common QAA2330 EWxC 2 Temperature 3 Temp_Common 7 LON1 8 LON2 QAA23SS EWxN 1 DC or ACH 2 DC or ACN GND 3 Temperature Out...

Страница 6: ...300 100 VA DC ACH DC ACN GND Signal Out Powered By Class 2 100VA Isolated AC L N E With Class 2 100 VA Output Isolated AC Supply See Controller Installation Instructions L N E Note See Caution NOTE Externally AC powered 2300 Room Units require controller common and all AC secondary neutral ACN to be earth grounded and may be used on the same controller with other room units powered by internal sen...

Отзывы: